5.8 AIR FLOW FAULT TESTS

These tests check the operation of the Blower Proof switch and Blocked Inlet switch shown in
Figure 5-4.
1.
Disable the blower output drive voltage as follows:
Press the MENU key until CONFIGURATION MENU is displayed.
(a)
Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then
(b)
press the CHANGE key.
Press the ▼ arrow key until OFF is displayed, then press the ENTER key.
(c)
2.
Start the unit in the Manual mode at a valve position of 25%.
3.
The unit should shut down and execute an IGNITION RETRY cycle by performing the
following steps:
The unit will execute a 30 second re-ignition delay and display WAIT RETRY
(a)
PAUSE.
The unit will then execute a standard ignition sequence and display WAIT
(b)
IGNITION RETRY.
Page 66 of 174
11/15/2016
CHAPTER 5 – SAFETY DEVICE TESTING
Flame Fault Tests – Continued
Air Flow Fault Tests
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
SSOV
TO AIR/FUEL VALVE
LOW GAS
PRESSURE
SWITCH
OMM-0120_0A
GF-128-I

Advertisement

Table of Contents
loading

Table of Contents