Modulex EXT Vent and Combustion Air Application Guide CHAPTER 1: CODES, SAFETY, AND VENTING SYSTEMS 1.1. APPLICABLE FEDERAL CODES United States: NFPA 54/ANSI National Fuel Gas Code Z223.1: NFPA/ANSI 211: Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances Canada: CAN1-B149.1: Installation Codes for Gas-Burning Equipment B149.2: Installation Codes for Gas-Burning Equipment...
Modulex EXT Vent and Combustion Air Application Guide 1.2. GAS VENT CATAGORIES WARNING! The Modulex boiler is approved for a Category IV vent configuration as well as for sealed combustion installations. Make provisions for combustion and ventilation air in accordance with Section 5.3, (Air for Combustion and Ventilation) of the National Fuel Gas Code - ANSI Z223.1, or Sections 7.2, 7.3, or 7.4 of CAN/CGA B149, Installation Codes, or applicable provisions of the local building codes.
Modulex EXT Vent and Combustion Air Application Guide 1.4. FACTORY SUPPLIED INLET AND VENT COMPONENTS For installation flexibility, venting connectors are provided for left hand, right hand, and rear connections. Basic drawings of the connection components and optional assemblies are shown in Figures 1 through 4.
Modulex EXT Vent and Combustion Air Application Guide 1.4.3. Flue Exhaust Piping Starter Pieces Table 1 lists the exhaust vent adaptors available for each Modulex EXT model. Instructions for assembling the vent adaptors are in Chapter 3. TABLE 1: EXT Vent Adaptors BOILER MODELS DIAMETER MATERIAL...
Modulex EXT Vent and Combustion Air Application Guide 1.4.4. Air Intake Connector (Supplied) Air is drawn into the EXT through the air inlet on the left side of the unit (Figure 4). A connector is included installed and ready to use for connecting the appropriate air intake piping for EXT 321– 1123/450–1100.
Modulex EXT Vent and Combustion Air Application Guide CHAPTER 2: COMBUSTION AIR SYSTEM WARNING! Air openings to combustion area must not be obstructed. Using Table 2, air openings may be specified so that adequate combustion air can be maintained. 2.1. COMBUSTION AIR REQUIREMENTS WARNING! •...
Page 10
Modulex EXT Vent and Combustion Air Application Guide 3. When combustion air is brought from outside the building and the boiler room is provided with two permanent openings, one shall commence 12 inches from the top and the other shall commence within 12 inches from the bottom of the room (see Figure 5).
Page 11
Modulex EXT Vent and Combustion Air Application Guide 7. When terminating the combustion air through the roof: a) Combustion air inlet must be 3 ft. below any vent outlet within 10 ft. See Figures 6 and 7. b) Combustion air inlet must also face away from the vent outlet. See Figure 6. Figure 6: Combustion Air Roof Termination Locations 8.
Modulex EXT Vent and Combustion Air Application Guide Bird Screen Installed Figure 8: Outdoor Installation Air Inlet and Vent Outlet Locations 11. For outdoor installations, an outdoor venting kit is available through AERCO. Please contact your local representative for further details. 2.2.
Modulex EXT Vent and Combustion Air Application Guide EXAMPLES: 1. A 40 foot length of combustion air pipe and 1 sharp 90° elbow plus two termination 90° elbows add up to 40 ft. + 10 ft. + (2 x 10 ft.) = 70 equivalent ft. (21.3 m). 2.
Page 14
Modulex EXT Vent and Combustion Air Application Guide EXAMPLES: The combustion air system of two EXT 1123/1100 (2 x 1,123,000 BTU/hr. = 2,246,000 BTU/hr.) consists of 30 foot length of common combustion air pipe and 3 sharp 90° elbows. The termination includes two (2) 90°...
Page 15
Modulex EXT Vent and Combustion Air Application Guide Figure 10: Typical Common Combustion Air Inlet installation Through Wall TAG-0054_0F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 15 of 28 GF-136–V Phone: 800-526-0288 09/25/2017...
Modulex EXT Vent and Combustion Air Application Guide CHAPTER 3: VENT SYSTEM Correct boiler venting is crucial for proper operation. Being a condensing boiler, combustion gases are discharged at a very low temperature. It is therefore necessary for the venting system to be impermeable to combustion products and condensate and to be made of corrosion resistant materials.
Page 17
Modulex EXT Vent and Combustion Air Application Guide EUROPEAN FLUE EXHAUST MANIFOLD (SUPPLIED) FLUE ADAPTOR GASKET (SUPPLIED) NUTS (6) (SUPPLIED) Figure 11: Connection of Exhaust Manifold to Flue Exhaust Outlet (EXT 321 – 1123) EUROPEAN FLUE EXHAUST MANIFOLD (SUPPLIED) FLUE ADAPTOR GASKET (SUPPLIED)
Page 18
Modulex EXT Vent and Combustion Air Application Guide GASKET FOR FLUE ADAPTOR EUROPEAN-TO-USA FLUE EXHAUST ADAPTER (SUPPLIED) EUROPEAN FLUE EXHAUST MANIFOLD INSPECTION PORT Figure 13: Assembly of USA Adaptor to European Flue Manifold (EXT 321 – 1123) GASKET FOR FLUE ADAPTOR EUROPEAN-TO-USA FLUE EXHAUST...
Page 19
Modulex EXT Vent and Combustion Air Application Guide OPTIONAL FLUE PIPING STARTER PIECE WORM-DRIVEN HOSE-CLAMP BOLT (4) WASHER (4) ADAPTOR CONNECTOR (4” or 6”, PVC or SS) GASKET EUROPEAN-TO-USA FLUE ADAPTER EUROPEAN EXHAUST MANIFOLD Figure 15: Flue Piping Starter Piece Assembly (EXT 321 – 1123) TAG-0054_0F AERCO International, Inc.
Modulex EXT Vent and Combustion Air Application Guide NOTE: Specific installation regulations for side-wall and vertical terminations, respectively, are described in the following two sections (Sections 3.2 and 3.3). 3.2. INSTALLATION PROCEDURE FOR VENTING SYSTEM THROUGH WALLS The minimum distances from adjacent public walkways, adjacent buildings, operable windows and building openings shall not be less that those values specified in the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CGA B149, Installation Codes.
Page 23
Modulex EXT Vent and Combustion Air Application Guide Figure 19: Determining Location of Vent Outlet TAG-0054_0F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 23 of 28 GF-136–V Phone: 800-526-0288 09/25/2017...
Modulex EXT Vent and Combustion Air Application Guide 3.3. INSTALLATION PROCEDURE FOR VERTICAL VENTING WARNING! Do not insulate or otherwise wrap vent pipe or fittings. Follow the vent pipe manufacturer’s installation instructions for vertical venting. WARNING! Non-motorized louvers and grilles must be fixed in an open position. Minimum screens mesh size shall not be smaller than ¼...
Modulex EXT Vent and Combustion Air Application Guide 3.4. VENT PIPING SIZE The maximum length is the combined length of straight horizontal and vertical runs, and the equivalent straight length of fittings. The required lengths for each boiler are as shown on Table 5 and TABLE 5: Venting Pipe Run Lengths EQUIVALENT VENT LENGTH EXAMPLES MAXIMUM...
Modulex EXT Vent and Combustion Air Application Guide 3.5. COMMON VENT PIPING SIZE Refer to Figures 6, 7 and 8 in Section 2 for typical common vent installations. The maximum length is the sum of the equivalent straight length of horizontal runs, vertical runs, and fittings of the individual vent connector and the common vent pipe.
Page 27
Modulex EXT Vent and Combustion Air Application Guide The maximum pressure drop of the combustion air piping is also 100 equivalent feet (30.5 m). See Section 2.3. Note that this does NOT mean that the allowed combined pressure drop between the vent and combustion air is 200 equivalent feet (61 m).