Tuning Menu; Combustion Cal Menu; Bmk 750/1000 Combustion Cal Menu - Watts AERCO Benchmark BMK 1500DF User Manual

Natural gas, propane gas, or dual fuel fired modulating, condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Operation, Service & Maintenance Guide-Latin America
SECTION 2: OPERATION

2.7 TUNING Menu

The Tuning menu items are Factory set for each individual unit. Do not change these menu
entries unless specifically requested to do so by factory-trained personnel.
A full description of each item appears in Appendix A-4.
TABLE 2-5: TUNING Menu
MENU ITEM DISPLAY
1
Prop Band
2
Integral Gain
3
Derivative Time
4
Warmup Prop Band
5
Warmup Int Gain
6
Warmup PID timer
7
Reset Defaults?

2.8 COMBUSTION CAL Menu

The Combustion Cal (Calibration) menu is protected by the level 2 password (6817) which must
be entered to view or change the menu items shown in Table 2-6, 2-7 and 2-8. These menu
items are used to vary the speed of the unit's blower motor based on air temperature and air
density at prescribed Air/Fuel Valve positions (% open). This is accomplished by providing a DC
drive voltage to the motor, which then adjusts the rotational speed of the blower to maximize
combustion efficiency and ensure the unit conforms to the Nitrogen Oxide (NO
Monoxide (CO) emissions specified in the combustion calibration instructions in Section 4.4 of
the Benchmark 750 – 3000 Installation and Startup Guide, OMM-0131 (GF-205-LA).
CAL Voltage values are factory adjusted for each unit prior to shipping, and so may differ from
the defaults shown in the tables below. A full description of each item appears in Appendix A-5.

2.8.1 BMK 750/1000 COMBUSTION CAL Menu

TABLE 2-6: COMBUSTION CAL Menu: BMK 750/1000
MENU ITEM DISPLAY
CAL Voltage 18%
1
CAL Voltage 30%
2
CAL Voltage 45%
3
CAL Voltage 60%
4
CAL Voltage 80%
5
CAL Voltage 100%
6
SET Valve Position
7
Blower Output
8
Set Stdby Volt
9
Oxygen Level
10
OMM-0132A
GF-206-LA-LA
MINIMUM
1°F (0.55°C)
0.00
0.0 min
1°F (0.55°C)
0.00
0 sec.
Yes, No, Are You Sure?
MINIMUM
0.25
0.25
0.25
0.25
0.25
0.25
0%
Monitor Blower Output Voltage
0 V
0%
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
MAXIMUM
120°F (66°C)
70°F (38.5°C)
2.00
2.00 min
120°F (66°C)
95 °F (52°C)
2.00
240 sec.
MAXIMUM
Natural gas
10.00
2.10
10.00
2.55
10.00
3.10
10.00
3.50
10.00
4.60
10.00
5.60
100%
0%
0.00
10.0 V
2.00
25%
0.0
DEFAULT
1.00
0.0min
0.50
20 sec.
No
) and Carbon
x
DEFAULT
Propane
2.10
2.55
3.10
3.50
4.60
5.60
0%
0.00
2.00
0.0
Page 21 of 162
01/02/2018

Advertisement

Table of Contents
loading

Table of Contents