CHAPTER 9 – OPERATION

9.15 User Menu

Press and hold the RESET button for 5 seconds to invoke the User Menu. When entering the
User Menu, the 1000 series of parameters, shown in the chart below, are available for display, but
cannot be edited.
Parameters for "Burner 1" are applicable for that burner only. If you want to see the same
parameters for the other burners you must connect the display to the burner you want to see per
the illustration in Figure 8-3. Parameters labeled "MULTIBURNER" apply to the entire unit. To
navigate the Installer Menu, perform the following:
Press the buttons
in the User Menu may be displayed, but cannot be edited.
PAR#
1001
Burner 1 supply temperature
1002
Indirect water heater temperature
1004
Outdoor sensor temperature (Boilers Only)
1006
Burner 1 Flue gas temperature
1007
Burner 1 Return temperature
1008
Burner 1 Ionisation current
1009
State of the General pump (and of the Burner 1 check valve)
1010
State of the CH pump (Boilers Only)
1011
State of the DHW pump
1012
Calculated CH setpoint (when outdoor sensor s activated) (only for 199 and 250 mode)
{Boilers Only)
1040
Burner 1 Actual Fan speed
1041
Burner 1 Ignition fan speed
1042
Burner 1 Low power fan speed
1043
Burner 1 High power fan speed
1051
Burner 1 Last lockout number
1052
Burner 1 Last Blocking error
1053
Burner 1 Number of flame failures
Burner 1 Number of failed ignitions
1055
1056
Burner 1 Total hours of operation tor boiler
1057
Burner 1 Total hours of operation for DHW
*Burner 1 Interval between Lockouts.
1059
May be: 1MIN; 2:HRS; 3:0AY; 4:WK
*Burner 1 Interval between Blocking errors.
1060
May be: 1:MIN; 2:HRS; 3:DAY; 4:WK
1062
Burner 1 Heating Water flow
1101
MULTIBURNER: Number of burners ON
1102
MULTIBURNER: System temperature ·
1103
MULTIBURNER: My Burner Into Lockout
1104
MULTIBURNER: Any Sumer into Stocking Error
1106
MULTIBURNER: System is in emergency mode
1107
MULTIBURNER: Current multi-burner setpoint
1120
MULTIBURNER: Burner 1 fire rate
1121
MULTIBURNER: Burner 2 fire rate
1122
MULTIBURNER: Burner 3 fire rate
1123
MULTIBURNER: Burner 4 fire rate
*Examples of displayed timer values and equivalent time lengths:
1:29 = 29 minutes
2:12 = 12 hours
OMM-0100_E • GF-146 • 11/15/2019
User Menu Navigation
and
to scroll through each of the parameters. All parameters
User Menu
PARAMETER'S DESCRIPTION
3:15 = 15 days
4:26 = 26 weeks
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
For parameters 1059 and 1060, the first digit displays the unit used, and
the second digit displays the number of those units. For example 1:34
would mean 34 minutes. A display of 4:3 would indicate 3 weeks.
UNITS
°F
°F
°F
°F
°F
µA
ON/OFF
ON/OFF
ON/OFF
°F
rpm/min
rpm/min
rpm/min
rpm/min
\
\
#
#
Hr x 10
Hr x 10
GPM
n
°F
/
/
/
°F
%
%
%
%
Page 110 of 170