3.7. TUNING MENU

The Tuning Menu items in Table 3-5 are Factory
set for each individual unit. Do not change these
Menu Item Display
Prop Band
Integral Gain
Derivative Time
Reset Defaults?

3.8. START SEQUENCE

When the Control Box ON/OFF switch is set to
the ON position, it checks all pre-purge safety
switches to ensure they are closed. These
switches include:
• Safety Shut-Off Valve Proof of Closure
(POC) switch
• Low Water Level switch
• High Water Temperature switch
• High Gas Pressure switch
• Low Gas Pressure switch
If all of the above switches are closed, the
READY light above the ON/OFF switch will light
and the unit will be in the Standby mode.
When there is a demand for heat, the following
events will occur:
NOTE:
If any of the Pre-Purge safety device switches
are open, the appropriate fault message will be
displayed. Also, the appropriate fault messages
will be displayed throughout the start sequence,
if the required conditions are not observed.
1. The DEMAND LED status indicator will light.
2. The unit checks to ensure that the proof of
closure switch in the Safety Shut-Off Valve
(SSOV) is closed (Figure 3-3).
CONTROL PANEL OPERATING PROCEDURES
menu entries unless specifically requested to do
so by Factory-Trained personnel.
Table 3-5. Tuning Menu
Available Choices or Limits
Minimum
1°F
0.00
0.0 min
Yes
No
Are You Sure?
3. With all required safety switches closed, a
Maximum
Default
120°F
70°F
2.00
1.00
2.0 min
0.0 min
No
Figure 3-3.
Safety Shut-Off Valve
purge cycle will be initiated and the following
events will occur:
3-7