CHAPTER 8 – WATER HEATER MANAGEMENT
WHM MENU
Set the minimum address of the heaters to be controlled by the
master. The WHM Min Addr and WHM Max Addr must differ by no
more than 7.
Set the maximum address of the heaters to be controlled by the
master. The WHM Min Addr and WHM Max Addr must differ by no
more than 7.
The Modbus Address of the SSD Device (ProtoNode). Set this
address to 247 if the WHM system is being monitored by a ProtoNode
with Slave –Slave (SSD) programming. Set to zero (0) if no
ProtoNode is installed.
SSD temp values can be accessed in Degrees or Points
Displays the valve status of all the units.
0= valve closed
1= valve open
2= valve stuck closed
3= valve stuck open
Display Comm Errors of all the units.
Specifies the WHM On and Off time delays associated with the Next
ON VP and Next OFF VP menu options. Therefore, if the Next ON VP
or Next OFF VP is at its preset Valve Position (%) for the specified
Delay period, another heater will be turned ON or OFF. This is done
to prevent cycling units on and off during short changes in load.
This value is a Factory debugging tool.
Specifies the Minimum number of units required to be "on" or "active".
Specifies the time a valve will remain closed when turning on a unit in
order to assure that we do not release cold water into the building.
When turning on a unit, the valve will open when either the Warmup
Timer times out or the FeedForward Temperature reaches Setpoint.
Specifies the time the WHM Master waits for a slave unit to turn On.
Displays the status of the WHM Sequencing Valve.
(1 = ON, 0 = OFF)