8.8.4 Control and Power Wiring
Control and power wiring connections to the sequencing valves associated with each C-More
WHM unit is accomplished by simply ensuring that the 4-pin Molex connectors on the units are
connected to the corresponding connectors on the valves.
Page 120 of 174
11/15/2016
CHAPTER 8 – WATER HEATER MANAGEMENT
Figure 8-4 WHMS Network Wiring Diagram
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
NOTES:
Wiring to be shielded
twisted-pair cable (Belden
9841 or equivalent).
Complete the following
instructions:
1. Activate DIP 1 (Modbus
TERM) on the first and
last units in the daisy
chain.
2. Tie incoming/outgoing
shields together and
terminate at the shield
terminal of the LAST
WHMS slave in the chain.
3. On the CPU board inside
the C-More Control Panel
of the last unit on the
chain, turn the DIP
OMM-0120_0A
GF-128-I