Watts Aerco Innovation 800 User Manual page 55

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
NATURAL GAS Combustion Calibration - Continued
22.
Once the oxygen level is within the specified range at 100%, press the ENTER key to store
the selected blower output voltage for the 100% valve position. Record all readings on the
Combustion Calibration Sheets provided.
23.
Repeat steps 16 through 21 for the following valve positions (see NOTE below):
80%, 60%, 50%, 40%, 30%, 20%, 16%
If NOx readings exceed the target values shown (<99 ppm), increase the O
level up to 25% higher than the listed calibration range shown in the table.
Record the increased O
Valve
Position
INN 1060
100%
6.0% ± 0.2%
80%
5.4% ± 0.2%
60%
5.4% ± 0.2%
50%
7.0% ± 0.2%
40%
7.0% ± 0.2%
30%
7.0% ± 0.2%
20%
6.5% ± 0.2%
16%
6.0% ± 0.2%
24.
If the oxygen level at the 16% valve position is too high and the Blower voltage is at the
minimum value, you can adjust the idle screw (TAC valve), which is recessed in the top of
the Air/Fuel Valve. Rotate the screw 1/2 turn clockwise (CW) to add fuel and reduce the O
to the specified level. Recalibration MUST be performed again from 60% down to 16%
after making a change to the idle screw (TAC valve).
Figure 4-5. TAC Valve (Idle Screw) Adjustment
This completes the NATURAL GAS combustion calibration procedure.
OMM-0120_0A
GF-128-I
CHAPTER 4 – INITIAL START-UP
value on the Combustion Calibration sheet.
2
Combustion Calibration Readings
Oxygen (O
) %
2
INN 800,
INN 1350
5.0% ± 0.2%
5.5% ± 0.2%
5.5% ± 0.2%
6.0% ± 0.2%
6.5% ± 0.2%
6.0% ± 0.2%
6.0% ± 0.2%
5.5% ± 0.2%
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
NOTE
Nitrogen
Oxide
(NOx)
<20 ppm
<20 ppm
<20 ppm
<20 ppm
<20 ppm
<20 ppm
<20 ppm
<20 ppm
- INTERNATIONAL
2
Carbon
Flame
Monoxide
µA
(CO)
<100 ppm
> 6
<100 ppm
> 6
<100 ppm
> 6
<100 ppm
> 6
<100 ppm
> 6
<100 ppm
> 5
<100 ppm
> 4
<100 ppm
> 2
TAC VALVE
IDLE SCREW
Page 55 of 174
11/15/2016
2

Advertisement

Table of Contents
loading

Table of Contents