Watts Aerco Innovation 800 User Manual page 138

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
APPENDIX B – STARTUP, STATUS AND FAULT MESSAGES
FAULT MESSAGE
AIRFLOW FAULT
DURING PURGE
AIRFLOW FAULT
DURING IGN
AIRFLOW FAULT
DURING RUN
DELAYED
INTERLOCK OPEN
DIRECT DRIVE
SIGNAL FAULT
FFWD TEMP
SENSOR FAULT
FLAME LOSS
DURING IGN
FLAME LOSS
DURING RUN
HEAT DEMAND
FAILURE
HIGH EXHAUST
TEMPERATURE
GAS PRESSURE
FAULT
HIGH WATER
TEMPERATURE
HIGH WATER TEMP
SWITCH OPEN
IGN BOARD
COMM FAULT
IGN SWITCH CLOSED
DURING PURGE
IGN SWITCH OPEN
DURING IGNITION
INTERLOCK
OPEN
LINE VOLTAGE
OUT OF PHASE
LOW WATER
LEVEL
NETWORK COMM
FAULT
Page 138 of 174
11/15/2016
Table B-2. Fault Messages
The Blower Proof switch opened during purge,
or air inlet is blocked.
The Blower Proof switch opened during ignition.
The Blower Proof switch opened during run.
The Delayed Interlock is open.
The direct drive signal is not present or is out of range.
The temperature measured by the Feed Forward (FFWD)
Sensor is out of range.
The Flame signal was not seen during ignition or lost within 5
seconds after ignition.
The Flame signal was lost during run.
The Heat Demand Relays on the Ignition board failed to activate
when commanded.
The High Exhaust Temperature Limit switch is closed.
The High Gas Pressure Limit switch OR Low Gas Pressure Limit
switch is open.
The temperature measured by the Outlet Sensor exceeded the
Temp Hi Limit setting.
The High Water Temperature Limit switch is open.
A communication fault has occurred between the PMC board
and Ignition board.
The Ignition Position Limit switch on the Air/Fuel Valve closed
during purge.
The Ignition Position Limit switch on the Air/Fuel Valve opened
during ignition.
The Remote Interlock is open.
The Line (Hot) and Neutral wires are reversed.
The Low Water Cutoff board is indicating low water level.
The RS-485 network information is not present or is corrupted.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
FAULT DESCRIPTION
OMM-0120_0A
GF-128-I

Advertisement

Table of Contents
loading

Table of Contents