Use PVC, stainless steel, aluminum or polypropylene for condensate drain
piping (Figure 2-7). DO NOT use carbon or copper components.
Two different styles of condensate traps are currently in use. The functions
and connections provided are nearly identical however they look slightly
different.
CONDENSATE
TRAP
ADAPTER
1"
INTERNAL
(2.54 cm)
I.D. HOSE
& CLAMP
TO
FLOOR
DRAIN
SUPPOR
Housekeeping pad should not extend under the condensate assembly
As a general guideline, AERCO recommends use of its Condensate
Neutralizer Kit to raise the pH level of the condensate prior to drainage. At
a minimum, the installation must be designed in accordance with local
codes that specify acceptable pH limits. For more information, see
Technical Instruction Document TID-0029, Condensate Neutralization Kit
and TID-0074 Condensate Neutralization Tank.
OMM-0120_0A
GF-128-I
CHAPTER 2 – INSTALLATION
--CAUTION -
EXHAUST
MANIFOLD
WITH
3/4"
(1.91 cm)
NIPPLES
LEFT SIDE VIEW
Figure 2-7. Sample Condensate Trap Installation