Watts Aerco Innovation 800 User Manual page 44

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
Menu Item Display
4
IGN Position
5
FFWD Temp Disply
6
Outlet Tmp Dsply
7
Inlet Tmp Dsply
8
Valv Pos Out Dsp
9
Exhaust Tmp Dsp
10
VP Up Rate
11
VP Down Rate
12
Purge Blwr Offst
13
4-20mA Purge Pct
14
PWM In Adj
15
Analog In Adj
16
Flow In Adj
17
Supply Gas Pressure In Adj
18
Gas Plate dp In Adj
19
mA Out Adj
20
A/F Sensitivity
21
Power Reset
22
Water Temp Reset
23
Gas Press Reset
24
Min Off Time
25
Heatr Tuning Dsp
26
Heatr Bkpt Dsp
27
Stop Level
28
Start Level
29
Skip Range Cntr
30
Skip Range Span
31
Skip Speed
32
O2 Gain
33
O2 Offset
34
O2 Sensor
35
Cal Temp Sensors
36
FFWD Temp Offset
37
Exhst Tmp Offset
38
Outdr Air Offset
39
Inlet Air Offset
Page 44 of 174
11/15/2016
CHAPTER 3 – OPERATION
Available Choices or Limits
Minimum
5%
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
0.5
0.5
-1.0
60%
-5.0%
-5.0%
-5.0%
-5.0%
-5.0%
-1.0 mA
1%
Automatic or Manual
Automatic or Manual
Automatic or Manual
0 Min
Enabled or Disabled
Enabled or Disabled
0%
Stop Level
10
0
5
920
-3.0
Enabled or Disabled
Enabled or Disabled
-20
-20
-20
-20
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
Maximum
60%
Depends on unit type/size
60.0
Depends on unit type/size
60.0
Depends on unit type/size
8.0
Depends on unit type/size
100%
5.0%
5.0%
5.0%
5.0%
5.0%
1.0 mA
5%
15 Min
Start Level
40%
95
3
20
1126
+3.0
Depends on unit type/size
+20
+20
+20
+20
Default
70%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0 mA
2%
Automatic
Automatic
Manual
0 Min
Disabled
Disabled
16
20
40
0
5
1024
0
0
0
0
0
OMM-0120_0A
GF-128-I

Advertisement

Table of Contents
loading