Watts Aerco Innovation 800 User Manual page 134

Gas-fired hot water boilers
Table of Contents

Advertisement

Innovation Hot Water Hot Water Boiler User Manual
APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Table A-5: CALIBRATION MENU ITEM DESCRIPTIONS
See section 3-8 for a range of choices and the default values.
MENU LEVEL & OPTION
22
Water Temp Reset
23
Gas Press Reset
24
Min Off Time
25
Heatr Tuning Dsp
26
Heatr Bkpt Dsp
27
Stop Level
28
Start Level
SKIP FEATURE:
Items 29 – 31 embody a feature that allows the user to define a Fire Zone the C-More will avoid. In
the rare instance when a unit emits an objectionable noise at a certain Fire Rate and no other remedy
solves the problem, a Fire Rate skip zone may be defined to command the C-More to Skip-Over the
defined Fire Rate.
29
– Skip Range CNTR
30
– Skip Range Span
31
– Skip Speed
O2 Settings:
Items 32 – 34 allow calibration of oxygen readings.
32
– O2 Gain
33
– O2 Offset
34
– O2 Sensor
35
Cal Temp Sensors
Temperature Channel Offset:
Items 36 – 41 embody the feature, which allow the user to field calibrate all six temperature channels
by entering an offset corresponding to the desired temperature channel.
36
– FFWD Temp Offset
37
– Exhst Tmp Offset
38
– Outdr Air Offset
39
– Inlet Air Offset
40
– Inlet Wtr Offset
Page 134 of 174
11/15/2016
Allows the Water Temperature Reset function to be set to AUTO or
MANUAL.
Allows the Gas Pressure Reset function to be set to AUTO or
MANUAL.
Allows the minimum Off time to be set from 0 to 10 minutes.
Allows Heater Tuning Display to be Enabled or Disabled.
Allows Heater Breakpoint Display to be Enabled or Disabled. When
Enabled, Breakpoints can be viewed and/or changed.
Allows the Stop Level to be set to a valve position ranging from 0% to
the presently set Start Level.
Allows the Start Level to be set to a valve position ranging from the
presently set Stop Level to a maximum of 40%.
Defines the Center (Fire Rate) of the skip band.
Defines the + and – band of the Skip Zone Size.
Defines the speed (Seconds/Fire Rate) at which the band will be
skipped.
Range = 0.1 to 1.5. (Unity Gain, No Mods)
Range = -3.0 to +3.0.
Enables the O2 Sensor
Allows calibration of the temperature sensor
Range = ± 20 ºF (± 11.1 °C)
Range = ± 20 ºF (± 11.1 °C)
Range = ± 20 ºF (± 11.1 °C)
Range = ± 20 ºF (± 11.1 °C)
Range = ± 20 ºF (± 11.1 °C)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
- INTERNATIONAL
DESCRIPTION
OMM-0120_0A
GF-128-I

Advertisement