Siemens SITRANS F M MAG 5000 Operating Instructions Manual

Siemens SITRANS F M MAG 5000 Operating Instructions Manual

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F M MAG 5000:
Table of Contents

Advertisement

SITRANS F
Electromagnetic flowmeters
SITRANS F M MAG 5000/6000
Operating Instructions
Edition
12/2013
Answers for industry.

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS F M MAG 5000

  • Page 1 SITRANS F Electromagnetic flowmeters SITRANS F M MAG 5000/6000 Operating Instructions Edition 12/2013 Answers for industry.
  • Page 3 ___________________ SITRANS F M MAG 5000/6000 Introduction ___________________ Safety notes ___________________ Description SITRANS F ___________________ Installing/Mounting Flowmeters ___________________ SITRANS F M MAG 5000/6000 Connecting ___________________ Commissioning Operating Instructions ___________________ Functions ___________________ Alarm, error, and system messages ___________________ Service and maintenance...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Connecting .............................. 35 Electrical connection ........................36 Electrical connection PTB K7.2 ....................38 Connection of add-on modules ....................38 Commissioning ............................39 MAG 5000/6000 Blind ........................39 Local user interface ........................40 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 6 Cable requirements ........................72 Spare parts/Accessories .......................... 73 12.1 Ordering ............................73 12.2 Accessories ..........................73 12.3 Spare parts ..........................74 12.4 Sun shield............................ 74 Menu diagrams ............................75 Transmitter menu overview ......................75 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 7 60 Hz Dimension dependent ......................94 50 Hz Dimension dependent batch and pulse output settings ............ 96 60 Hz Dimension dependent batch and pulse output settings ............ 97 Approvals/Certificates ..........................99 Index ..............................101 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 8 Table of contents SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 9: Introduction

    It is the responsibility of the customer that the instructions and directions provided in the manual are read, understood and followed by the relevant personnel before installing the device. Items supplied SITRANS F M MAG 5000/6000 transmitter Calibration report SITRANS F literature CD Quick start guide Inspection 1.
  • Page 10: History

    ● SITRANS F MAG 5000 and MAG 6000 transmitters (standard version). ● Optional versions: – MAG 5000 Blind and MAG 6000 Blind – MAG 5000 CT and MAG 6000 CT – MAG 6000 SV SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 11: Further Information

    Product information on the Internet The Operating Instructions are available on the CD-ROM shipped with the device, and on the Internet on the Siemens homepage, where further information on the range of SITRANS F flowmeters may also be found: Product information on the internet (http://www.siemens.com/flow)
  • Page 12 Introduction 1.4 Further Information SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 13: Safety Notes

    50% relative humidity from 40°C (104°F) ● Main supply voltage fluctuations up to ±10% of the nominal voltage (see technical specifications) ● Overvoltage category II ● Pollution degree 2 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 14: Installation In Hazardous Location

    ● Electrical connections are in accordance with Elex V (VO in explosion hazardous areas) and EN60079-14 (Installing Electrical Systems in Explosion Hazardous Areas). ● The protective cover over the power supply is properly installed. For intrinsically safe circuits the connection area can be opened. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 15 ● EN50281-1-2 is considered for installation in areas with combustible dust. ● When protective earth (PE) is connected, no potential difference between the protective earth (PE) and the potential equalization (PA) can exist, even during a fault condition. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 16 Safety notes 2.2 Installation in hazardous location SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 17: Description

    Description System components A SITRANS F M MAG 5000/6000 flowmeter system includes: ● Transmitter (type SITRANS F M MAG 5000/6000) ● Sensor (types: SITRANS F MAG 1100/1100F/3100/3100 P/5100 W) ● Communication module (optional) (types: HART, PROFIBUS PA/DP, MODBUS RTU RS 485, Foundation Fieldbus H1, Devicenet) ●...
  • Page 18: Features

    Output module The output module converts flow data to analog, digital and relay outputs. The outputs are galvanically isolated and can be individually set to suit a particular application. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 19: Mag 5000/Mag 6000 Versions

    SV version (MAG 6000 only) This version is identical to the standard MAG 6000 transmitters except for the following additional functions: ● Zero point adjustment ● Adjustable excitation frequency up to 44 Hz SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 20 Description 3.5 MAG 5000/MAG 6000 versions SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 21: Installing/Mounting

    No further assembling is necessary. The transmitter can be installed either compact on the sensor or remote. Figure 4-1 Compact installation Figure 4-2 Remote installation SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 22: Installation Conditions

    Reading and operating the flowmeter is possible under almost any installation conditions because the display can be oriented in relation to the sensor. To ensure optimum flow measurement, attention should be paid to the following: Vibrations Figure 4-3 Avoid strong vibrations SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 23 Standard, blind and SV versions Figure 4-5 CT version Remote installation Cable length and type (as described in Cable requirements (Page 72)) must be used. For installation conditions for sensors, see respective sensor operating instructions. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 24: Mag 5000/6000 Compact

    System will not register flow if black plugs are not connected to connection board. 7. Fit supply and output cables through cable glands and connect to connection plate as shown in Electrical connection (Page 36). SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 25 11. Transmitter is ready to be powered up. NOTICE Exposing transmitter to direct sunlight may increase operating temperature above its specified limit, and decrease display visibility. A sunshield is available as accessory. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 26: Remote Installation

    1. Remove terminal box lid. 2. Remove SENSORPROM unit from sensor terminal box and mount it in terminal box of ® wall mounting unit. 3. Fit M20 or ½" NPT cable glands for cables. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 27 Unscreened cable ends must be kept as short as possible. Electrode cable and coil cable must be kept separate to prevent interference. 5. Tighten cable glands well to obtain optimum sealing. WARNING Mount terminal box lid before power up. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 28 Figure 4-6 Wall mounting Figure 4-7 Pipe mounting - vertical Figure 4-8 Pipe mounting - horizontal 2. Ensure that correct SENSORPROM memory unit is mounted in wall/pipe mounting unit. ® SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 29 6. Fit coil, electrode, supply and output cables through cable glands and connect to connection plate as shown in Electrical connection (Page 36). 7. Fix connection plate with the two diagonally opposite screws. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 30: Mag 5000/6000 Ct

    MAG 6000 CT is installed like a Standard MAG 6000 except for the final sealing. Calibration sealing has been carried out at calibration. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 31: Installing Hardware Key

    When key is mounted, access to all menu items is gained. When key is removed, primary settings are blocked in accordance with requirements in authorisation. 4.5.2 Seal device Seal transmitter CAUTION Seal transmitter to prevent unauthorized access. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 32 1. Seal connection plate to prevent access to SENSORPROM memory unit as shown ® below. 1 indicates sealing locations. 2. Drill through marked drilling holes in terminal box and transmitter/lid. Seal transmitter externally as shown below. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 33: Installation Conditions

    ● Compact or remote with max. 10 m (33 ft.) cable Other restrictions may apply (see certificate 22.76/10.02) **insert installation conditions as pasted Turning transmitter/keypad It is possible to alter the standard assembly, e.g. to turn transmitter or keypad. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 34 Terminal box can be rotated ±90° in order to optimize viewing angle of transmitter display/keypad 1. Unscrew the four screws in bottom of terminal box. 2. Turn terminal box to required position. 3. Retighten screws firmly. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 35 Installing/Mounting 4.6 Turning transmitter/keypad Keypad 1. Remove outer frame using a screwdriver. 2. Loosen the four screws retaining keypad. 3. Withdraw keypad and turn it to required orientation. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 36 Installing/Mounting 4.6 Turning transmitter/keypad 4. Tighten the four screws until a mechanical stop is felt in order to obtain IP67 enclosure. 5. Snaplock outer frame onto keypad (click). SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 37: Connecting

    For field wiring installation: Ensure that the National Installation Code of the country in which the flowmeters are installed is met. Note National installation code Observe country specific installation directives for field wiring. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 38: Electrical Connection

    Connecting 5.1 Electrical connection Electrical connection Figure 5-1 Wiring diagram SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 39 Fasten cables/wires in a way that they cannot get into contact with each other, not even in case of an error. Keep wire ends as short as possible. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 40: Electrical Connection Ptb K7.2

    91-97. For more information Refer to the relevant BUS communication Quick Start or Operating Instructions available at the SITRANS F literature CD or on the internet, at : www.siemens.com/flowdocumentation (www.siemens.com/flowdocumentation). SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 41: Commissioning

    All changed data will be stored in SENSORPROM memory unit. ® 4. Remove standard transmitter and remount Blind transmitter. 5. Fasten screws holding transmitter. New settings stored in SENSORPROM memory unit will be uploaded in blind transmitter. ® SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 42: Local User Interface

    Lock field Figure 6-1 Local User Interface Mode field symbols Communication mode Language mode Sensor characteristics Service mode Basic settings Reset mode Operator menu Output Operator-active Product identity External input Operator-inactive SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 43: Menu Structure

    2 seconds. The setup menu operates in two modes: ● View mode ● Setup mode View mode is a read-only mode. The pre-selected settings can only be scanned. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 44: Changing Password

    Factory setting of password can be re-established as follows: 1. Switch off power supply. 2. While pressing top up key - switch on power supply. 3. Release top up key after 10 sec. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 45: Changing Basic Settings

    6. Press lock/unlock key to unlock settings. 7. Use select key and change key to change settings. 8. Press lock/unlock key to confirm new settings. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 46 9. Repeat steps 5-8 to change other settings. 10. Press top up key two times to exit setup mode. Decimal point can be positioned and units set individually for flow rate in totalizer 1 and totalizer 2. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 47: Changing Operator Menu Setup

    2. Press lock/unlock key to unlock setting. 3. Use select key to move cursor to upper line. 4. Use change key to select requested reading. 5. Press lock/unlock key to confirm selection. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 48: Changing Language

    4. Press lock/unlock key to unlock language. 5. Use change key to select desired language. 6. Press lock/unlock key to confirm new language. 7. Press top up key two times to exit setup mode. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 49: Functions

    Alarm level Output 3.5 mA High 22.6 mA For setting of error level, see Error level menu diagram. If current output is not used, it must be set to "Off". SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 50 Not available in MAG 5000, MAG 5000 CT and MAG 6000 CT. Note Cleaning If a cleaning unit is installed together with transmitter, relay output must always be used to operate this unit. It cannot be used for other purposes. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 51: External Input

    ● Calibration factor. ● Correction factor. ● Excitation. See also sensor characteristics menu diagram. Reset mode The reset mode is used for resetting totalizers/counters or for restoring MAG 5000/6000 to its factory settings. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 52 4. Press lock/unlock key to enter reset menu. 5. Press forward key to reach zero adjust menu. 6. Press lock/unlock key to enter the menu. 7. Use change key to select "manual". SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 53: Service Mode

    ● Totalizer 1 cannot be reset. ● Totalizer 2 can be reset if the flow velocity in the meter pipe is <0.25 m/s. When the totalizer is reset, the pulse output register will also be reset. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 54: Mag 6000 Sv

    When this is done, the decrease in measuring accuracy can be kept below 1% o.r. A too high frequency for the sensor used will cause a coil current alarm indication. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 55: Alarm, Error, And System Messages

    The acceptance level for "error pending" can be individually configured to a particular application. The acceptance level is set in the basic settings menu (Page 43). SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 56 An output can also be selected to activate on a single error number. The alarm field, error output and error pending always operate together. Operator menu Error pending and status log are as default enabled ( ) in the operator menu. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 57: List Of Error Numbers

    P41 - Parameter range Switch off and on A parameter is out of range. The parameter could Active Active not be replaced by its default value. The error will disappear at the next power-on SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 58 It is not possible to read from the SENSORPROM Active Active ® unit anymore F70 - Coil current Check cables Coil excitation has failed Active Active F71 - Internal error Replace transmitter Internal convertion error in ASIC Active Active SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 59: Service And Maintenance

    It is a highly advanced instrument, which carries out the complex verification of the entire flowmeter system according to unique SIEMENS patented principles. The verification test is automated and the instrument easy to use, so no human error or influence will affect the verification.
  • Page 60: Technical Support

    Sensor check list Check list for sensors are included in the respective sensor operating instructions. Technical support NOTICE Repair and service must be carried out by approved Siemens Flow Instruments personnel only. Note Siemens Flow Instrument defines sensors as non-repairable products.
  • Page 61: Return Procedures

    ● Information about field service, repairs, spare parts and lots more under "Services." Additional Support Please contact your local Siemens representative and offices if you have additional questions about the device Find your contact partner at: Local contact person (http://www.automation.siemens.com/partner)
  • Page 62: Recalibration

    You can find the forms on the Internet and on the CD delivered with the device. Recalibration Siemens A/S Flow Instruments offers to recalibrate the sensor. The following calibrations are offered as standard: ● Standard matched pair calibration...
  • Page 63: Troubleshooting/Faqs

    Replace SENSORPROM unit or ® ® reset SENSORPROM unit with MAG ® CT transmitter Defective SENSORPROM Replace SENSORPROM unit ® ® unit Wrong type of Replace SENSORPROM unit ® SENSORPROM unit ® SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 64 Change pulse width Measuring approx. Missing one electrode Check cables connection Loss of totalizer data Initializing error Reset totalizer manually ##### Signs in Totalizer roll over Reset totalizer or increase totalizer display unit SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 65: Technical Data

    0 ... 9.9% of maximum flow Galvanic isolation All inputs and outputs are galvanically isolated Max. measuring error MAG 5000 0.4% ± 1 mm/s (for v > 0.1 m/s) (incl. sensor and zero point) SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 66 Prepared for client mounted add-on modules: HART, MODBUS RTU/RS485, FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA, PROFIBUS DP as add-on modules MAG 5000 CT / MAG 6000 CT No communication modules approved SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 67 Technical data 11.1 Technical specifications Transmitter IP67/NEMA 4X/6 compact polyamide Weight: MAG 5000/6000: 0.75 kg (1.65 lbs) Transmitter IP67/NEMA 4X/6 wall-mounted polyamide Weight(transmitter and wall mounting bracket): 1.65 kg (3.64 lbs) SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 68: Accuracy

    For accuracy reference conditions, please see below. Figure 11-1 MAG 5000 with MAG 1100, MAG 1100 F, MAG 5100 W, MAG 3100 and MAG 3100 P and MAG 6000 with MAG 1100 (PFA), MAG 1100 F (PFA) SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 69 10 x DN (DN ≤ 1200/48") 5 x DN (DN > 1200/48") Outlet section 5 x DN (DN ≤ 1200/48") 3 x DN (DN > 1200/48") Flow conditions Developed flow profile Reference conditions for sensor calibration SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 70: Output Characteristics

    ≥ 10 μS/cm Additions in the event of deviations from reference conditions 11.3 Output characteristics Current output Output characteristics Bidirectional mode Unidirectional mode 0...20 mA 4...20 mA Frequency output Bidirectional mode Unidirectional mode SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 71 Active Error relay output Bidirectional mode Unidirectional mode No error Error Limit switch (can be used as direction switch) 1 set point 2 set points Passive Digital output Passive Digital output SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 72 11.3 Output characteristics 1 set point 2 set points Note Active digital output is not avaiable with MAG 6000 I. Batch on digital output Unidirectional mode (forward flow only) Totalizer lap SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 73: Cable Data

    -5 ... +70°C (23 ... 158°F) (23 ... 158°F) Non-flexible installtaion -30 ... +70°C -30 ... +70°C (-22 ... 158°F) (-22 ... 158°F) Cable parameter Capacity 161.50 pF/m Inductance 0.583 μH/m 43.83 þH/Ω SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 74: Cable Requirements

    For Ex zone 1 installations only certified cable glands with protection type "e" can be used for the power supply and the coil cable. The cable glands must be approved for the actual temperature and cable dimension. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 75: Spare Parts/Accessories

    In order to ensure that the ordering data you are using is not outdated, the latest ordering data is always available on the Internet: Catalog process instrumentation (http://www.siemens.com/processinstrumentation/catalogs) 12.2 Accessories Description Wall mounting unit Display protection lid Communication modules for MAG 6000 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 76: Spare Parts

    Spare parts/Accessories 12.3 Spare parts 12.3 Spare parts Description Connection plate SENSORPROM memory unit ® Display unit Communication modules for MAG 6000 12.4 Sun shield Description Sun shield SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 77: A Menu Diagrams

    The menu diagrams shown on the following pages apply to MAG 5000/6000 as well as MAG 6000 I. Not available in MAG 5000 Add-on module Factory-set password: 1000 Not available when batch Only available when batch SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 78: Basic Settings

    The flow rate unit can be "?/?" or show customer unit texts as for example "AcrFt/y" (Acre feet/year). When batch is selected on digital output or relay, Totalizer 2 is not shown because it is controlled by the batch function. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 79: Current Output

    Do not combine differentiation and low alarm level together with passive output. The output will try to pull down the level to 1.3 mA at fatal errors which is not possible for passive output. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 80: Digital Output - Pulse

    Menu diagrams A.4 Digital output - pulse Digital output - pulse Digital output - frequency Error level SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 81: Error Number

    If digital output is set up for pulse, frequency or batch, then the relay output will be turned off if it has been set up for batch. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 82: External Input

    (The display is locked during this time). The time cycle can be set at 1 to 240 hours. If the cycle is set at for example three hours, the transmitter will be active every three hours. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 83: Sensor Characteristics

    In this case the power must be switched off/on to suppress the P40 error on the output. The frequency can be set to 44 Hz in the MAG 6000 SV transmitter only. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 84: Reset Mode

    Menu diagrams A.12 Reset mode A.12 Reset mode SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 85: Reset Mode - Mag 6000 Sv

    Menu diagrams A.13 Reset mode - MAG 6000 SV A.13 Reset mode - MAG 6000 SV SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 86: Service Mode

    9 is the best signal measured. If digital output is set to pulse (standard). If digital output is set to frequency. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 87: Operator Menu Setup

    2 and flow velocity is chosen in line 3, the text "Flow velocity " is shown in line2 and the measured flow velocity is shown in line 3. SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 88: Product Identity

    Menu diagrams A.16 Product identity A.16 Product identity SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 89: Add-On Communication Module

    Burst mode is not available with HART communication A.18 Cleaning Note Relay outputs If cleaning unit is installed, relay outputs must always be used to operate cleaning. Relay outputs cannot be used for other purposes SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 90: Mag 5000/6000 Ct Menu Overview

    Overview MAG 5000 CT and MAG 6000 CT (part 1) Factory-set password: 1000 Not visible when CT mode is "Hot water" Figure A-2 Overview MAG 5000 CT and MAG 6000 CT (part 2) SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 91: Change Password

    Menu diagrams A.20 Change password Note Sealing Menus marked with gray are locked when transmitter is sealed. A.20 Change password SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 93: B Factory Settings

    Current output Off for On/off, Unidirectional/bidirectional, 0...20 Output MAG5000/ mA/4...20 mA/4...20 mA + Alarm settings (Page 47) 6000 On for MAG6000I Namur High/Low Alarm level Yes/No Alarm diff. 0.1...30 s Time constant SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 94 0.1 s 0.1 ... 30 s Time constant External input External input Batch, reset totalizer, freeze output, forced output, External input (Page 80) Start Start, hold/continue, stop, Qmax 2 Batch SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 95: 50 Hz Dimension Dependent

    441.7864 150 (6) 15.74527 629.8107 15.90432 636.1725 200(8) 24.93797 997.5184 28.27434 1130.973 250(10) 40.00377 1600.15 44.17865 1767.145 300 (12) 1000 62.50395 2500.157 63.61726 254469 350 (14) 1200 86.59015 3463.605 86.59015 3463.605 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 96: B.3 60 Hz Dimension Dependent

    4778.363 191134.4 m3/h 280 (114) 65000 5541.77 221670.7 m3/h 3000 (120) 70000 6361.726 254469 m3/h * The min. and max. amount values show mathematical values and do not indicate measurement accuracy SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 97 US GPM 1200 (48) 66044 4481.574 179262.9 4481.574 179262.9 US GPM 1400 (54) 110072 6099.92 243996.7 US GPM 1500 (60) 1320867 7002.459 280098.3 US GPM 1600 (66) 154101 7967.242 318689.6 US GPM SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 98: 50 Hz Dimension Dependent Batch And Pulse Output Settings

    171.5728 m 125 (5) 9.265244 ml 242.8828 m 10.22654 ml 268.0825 m 150 (6) 14.57896 ml 382.1785 m 14.72622 ml 386.0389 m 200 (8) 23.09071 ml 605.309 m 26.17994 ml 686.2913 m SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 99: 60 Hz Dimension Dependent Batch And Pulse Output Settings

    5.890487 l 154415.5 m * The min. and max. amount values show mathematical values and do not indicate measurement accuracy. ** For CT devices the totalizer 1 unit is in m SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 100 4532475 0.1729003 4532475 1100 (44) 0.2092093 5484294 0.2092093 5484294 1200 (48) 0.2489763 6526764 0.2489763 6526764 1400 (54) 0.3388844 8883651 1500 (60) 0.3890255 10198060 1600 (66) 0.4426246 11603130 1800 (72) 0.5601967 14685210 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 101 US G max. US G min. US G max. 2000 (78) 0.6916009 18129900 2200 (90) 0.836837 21937170 2400 (96) 0.995906 26107050 2600 (102) 1.168806 30639530 2800 (114) 1.355538 35534600 3000 (120) 1.556102 40792270 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 103: C Approvals/Certificates

    Approvals/Certificates All certificates are posted on the Internet. Additionally, the CE Declaration of Conformity as well as ATEX approvals are available on the SITRANS F literature CD-ROM. Certificates (http://support.automation.siemens.com/WW/view/en/10806951/134200) SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 104 Approvals/Certificates SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 105: Index

    Service, 58, 59 Error handling, 53 Support, 59 System components, 15 Hotline, 58 Wire insulation, 35 Installation Indoor/outdoor, 19 Internet Contact person, 9, 59 Flow documentation, 9 Support, 59 Introduction, 7 SITRANS F M MAG 5000/6000 Operating Instructions, 12/2013, A5E02338368-002...
  • Page 106 For more information www.siemens.com/flow Siemens A/S Subject to change without prior notice Flow Instruments Order No.: A5E02338368 Nordborgvej 81 Lit. No.: A5E02338368-002 DK-6430 Nordborg © Siemens AG 12.2013 A5E02338368 A5E02338368 www.siemens.com/processautomation...

This manual is also suitable for:

Sitrans f m mag 6000

Table of Contents