Commissioning (block-oriented operation)
78
12
Commissioning (block-oriented operation)
12.1
Function check
Before commissioning your measuring point, ensure that the post-installation and post-
connection checks have been performed:
• "Post-installation check" checklist → 31
• "Post-connection check" checklist → 38
12.2
Block configuration
12.2.1
Preparatory steps
1. Switch on the measuring device.
2. Make a note of the DEVICE_ID.
3. Open the configuration program.
4. Load Cff and device description files into the host system or the configuration
program. Make sure you are using the right system files.
5. Identify the device using the DEVICE_ID (see Point 2). Assign the desired tag name
to the device via the Pd-tag/FF_PD_TAG parameter.
12.2.2
Configuring the Resource Block
1. Open the Resource Block.
2. If necessary, disable the lock for device operation.
3. If necessary, change the block name. Factory setting: RS-xxxxxxxxxxx (RB2)
4. If necessary, assign a description to the block via the Description of the
identification tag/TAG_DESC parameter.
5. If necessary, change other parameters as required.
12.2.3
Configuring the Transducer Blocks
The measurement and the display module are configured via the Transducer Blocks. The
basic procedure is the same for all Transducer Blocks:
1. If necessary, change the block name.
2. Set the block mode to OOS via the Block mode/MODE_BLK parameter, TARGET
element.
3. Configure the device in accordance with the measuring task.
4. Set the block mode to Auto via the Block mode/MODE_BLK parameter, TARGET
element.
The block mode must be set to Auto to ensure the smooth operation of the device.
Levelflex FMP55 FOUNDATION Fieldbus