4.2.8

S-Bus Connection Settings

1
Name
2
Type
3
S-Bus station
no.
4
Port
5
TCP/IP address
6
Error reason
7
Delete
8
Save
Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05
Default:
Enter a name for the S-Bus station.
*not defined*
Maximum 20 characters with no spaces or
special characters
Default:
Appears only if S-Bus name is defined.
none
■ Serial SBus
■ Ether SBus
Default: 0
Appears only if S-Bus name is defined.
 N.B. This is the S-Bus station number: 0 to
255
Default: 0
Appears only if Serial S Bus is selected.
■ Port 0 (RS-232)
■ Port 1 (RS-485)
Default: 0
Appears only if Ether S Bus is selected.
Enter the IP address of the station
Default:
List of error reasons:
none
Timeout
Slave not ready
Retry Expired
SBus Timeout
Rcv Failed
General Error
Delete parameters
Save parameters and return to S-Bus connec-
tions
Setup Menu QVGA MB-Panels
Setup Menu Configuration "step by step"
Potential source of communication
error
List of error reasons:
- Bad cabling. Most common error.
- Bad grounding. Can cause damage
to the interface!
- Connection to the wrong serial line.
- Incompatible transmission speed.
- Slave station not assigned.
- Slave station not started.
- Slave address mismatch.
- Defective interface (sender and/or
receiver).
- The Saia PCD
firmware does not
®
support this mode
See
See
See list of
error reasons
Web Server busy
above
No Web Server
Out of sequence
SBus NAK
Snd Failed
4
4-18