1.5

Installation of the mounting brackets

■ Mounting position is horizontal. CUT-OUT dimension : 189 × 142 mm or 262 × 202 mm
■ Slide the unit into the cut out hole
■ Make sure the ventilation slots (top of unit and both sides) are clear of any ob-
structions to allow air circulation
■ Install 4 mounting clamps for 5" and 5.7" (2 on top and 2 on the bottom), 6 clamps
for 7" and 10.4" (2 on top, 2 on the bottom and 2 on the sides) and 8 clamps for
the 12.1" (3 on top, 3 on the bottom and 2 on the sides)
Notes:
a) It is helpful to have somebody hold the unit from the front side of the panel
while the brackets are being installed
b) The screws require a hex wrench 2.5 mm
c) Advance the screws in the brackets up to the point where you can still clip them
onto the Microbrowser, without being obstructed by the plate
d) Clip them onto the unit then advance the screws until they touch the plate
e) The required torque to seal the gasket is 20cNm. Do not exceed 30cNm to
avoid breaking of the clamp
Photograph of mounting brackets installed on the bottom of the Microbrowser.
Mounting
surface / wall
How to insure a watertight according to IP65?
■ The device must be mounted on a flat surface/wall
■ Practically, tighten the screws until the front plate of the PCD7.D4xx slightly touch-
es the mounting surface/wall
Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05
Front plate of
PCD7.D4xx
Installation of the mounting brackets