List Of Message-Box Messages - SBC PCD7.D4 Series Manual

Mb-panel
Table of Contents

Advertisement

Saia-Burgess Controls AG
6.10

List of Message-Box messages

Messages
Out of memory in Ramdisk
Failed to parse .csv
LR: out of memory or out of memory for
language resource
Failed to initialize LR heap!
Failed to initialize heap 1
Out of memory in heap 1
Failed to initialize heap 2
Out of memory in heap 2
Out of memory in heap 3
Maximum number of object reached
Order Values on remote host has failed
ReadFile on remote host has failed
buffer OVF in Spider_fileReadln()
Range is null
value out of range
value out of default range
Reading UTF string failed;
Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05
Remarks
May appear if a file (most commonly a .gif) is too large.
VGA MB panel: < 256 Kb
(see also section 6.11)
Language
No memory is available to parse a .csv file.
No memory is available to parse a .csv file. or the total size
memory used is > 512 kbytes (see also section 6.11)
The memory for the .csv file will be initialized every time a
file is parsed. This message means it has failed.
Memory
On the heap1 the painter objects and the list of current
PPO's are allocated. This heap will be erased after each
.teq jump
the total size memory used by the painters is > 512 Kbytes
(see also the section 6.11)
On the heap 2 container variables, HTML tags and trending
data are stored. This heap will be initialized on every URL
jump.
The total size memory used by the html tags and containers
variable > 768 Kbytes. Most probable cause for this mes-
sage is that to many trends are active.
→ Can appears in case of online and offline trends.
The memory requirement must be calculated before using
trends
Example: In case of the Update period of process points
(web-editor parameter) = 1000 milliseconds
(store time in sec) x (total nber of trends) x (Size of one Data
point → 28 Bytes) < ~ 750 Kbytes
1800 sec x 12 trends x 28 Bytes = 600 Kbytes + size
memory used by html tags
the total size memory used by the offline trend and HD log
> 1024 kbytes (see also section 6.11)
Object
The maximum amount of objects (like buttons, rectangles
etc) in one .teq view has been exceeded. Maximum object
= 512
→ See also the definition of an object in section 10
PPO
Ordering of the list of current PPO's on the remote host has
failed.
Periodic polling of PPO's has failed.
Communication
During loading of a file more data has been received than
the buffer will hold.
The calculation of the range of a bar graph has been faulty.
TCR
The min/max limits of a TCR value have been exceeded.
The value of a TCR is not valid, foe example «aa» for hour.
TEQ
Probably the end of the file was reached during reading of a
string.
Update & special settings
List of Message-Box messages
6
6-27

Advertisement