S-Bus On Rs-485 - SBC PCD7.D4 Series Manual

Mb-panel
Table of Contents

Advertisement

Saia-Burgess Controls AG
2.5.2

S-Bus on RS-485

PCD7.D4xx
X5
Pining nr of each PLC connected is defined in their dedicated manual.
Termination resistors for proper End of line
In the example below, you see a possible interconnection between terminals and
PLCs. In order to avoid reflexions on the communication line please terminate the
network with termination resistors. On the PCD7.D4xx, a switch is avaiable:
First station
PCD1.M110
Port #1
Pull up
330 Ohm
Termination
Resistor
150 Ohm
Pull down
330 Ohm
The next image shows you where it is located.
When the switch is placed on the top position, the network is closed.
When the switch is placed on the bottom position, the network is open.
RS-485 switch
End Termination Switch
Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05
PCD3.M3/M5
Port #2 or 1 with PCD3.F110/F150
Middle stations
PCD1.M1xx
PCD2.Mxx0
+5 V
n
12
Bus RS485
11
PCD1:M125/135
Port #1
RS-485 Network connection
PCD1.M1xx
PCD2.Mxx0
/n
n
/n
/RX - /TX
RX - TX
Segment length max. 1200 m
max. 32 stations
Hardware-System Overview
Interface connection
PCD2.M150/M170/M480
Port #1 with PCD7.F110/F150 or Port 6 (M480)
End station
PCD7.D4xx
PCD1.M1xx
PCD2.Mxx0
+5 V
/n
n
2
2-6