Setting up communication to display a web page

1.6.1

HTTP direct via Ethernet RJ45 connection

The quickest communication connection is the Ethernet port via RJ45, if the protocol HTTP direct
was selected. The speed is either 10 MBit/s or 100 MBit/s with an auto-negotiation protocol via the
connected device.
Internal connection for programmable web panels
The programmable panels are connected internally via an Ethernet connection directly to the pro-
grammable logic controller. All that you need to do is set the local host IP address 127.0.0.1 and the
http direct connection under Web Connection in the Setup Menu. Naturally, the programmable web
panels can also display the web pages of controllers in the network.
Connecting to external devices
An HTTP connection can be established between our PCD7.D4xx and any Saia PCD
an Ethernet connection to the automation server exists. With the programmable panels, the panel is
generally connected to the internal controller.
1.6.2

Panel speed test

-
A web program generated with the Web Editor must first be loaded onto the Saia PCD
-
Connect the panel to the Saia PCD
auto-crossing, a crossover cable is no longer needed.
Setup settings for the PCD7.D443WTxRx panel:
For configuration, the Setup Menu must be open. (See Chapter 5):
-
First ensure that you are in the same network subnet. Example: If the Saia PCD
dress 192.168.12.92, enter an IP address such as 192.168.12.90 in your terminal (in the Network
Menu), because the subnet mask is usually 255.255.255.0.
-
In the Configuration Menu, enter the address of the start page which corresponds to the IP ad-
dress of the Saia PCD
The MB panel should now be connected to the Saia PCD
displayed on the monitor. You can now navigate through your web pages!
PCD7.D443WTxRx | Document 27-644 | Version ENG04 | 2017-10-30
Ethernet http direct
using a CAT5 cable. Because the current controllers support
®
and also the name of the HTML start page.
®
and the selected start page should be
®
®
controller if
®
.
®
has the IP ad-
14