  • Page 1 Manual S-Web-Editor with Web-Panel Web-Server Micro-Browser 10.4“ Comfort Line with Web-Server Web-Panel Micro-Browser 5.7“ Comfort Line with Web-Server Web-Panel Micro-Browser 5.7“ Base Line Series PCD7.D4xx MB-Panel Document 26-851; Edition ENG12 │ 2016-02-05...
  • Page 2: Table Of Contents

    Content Saia-Burgess Controls AG Index Index Document History ................... 0-5 Brands and trademarks ................. 0-5 Quickstart Introduction ..................... 1-1 1.2 Connectors definition ..................1-2 Power supply ....................1-2 Dimension and cut-out (all in mm) ..............1-3 Installation of the mounting brackets .............. 1-4 Operation and handling ..................
  • Page 3 Content Saia-Burgess Controls AG Setup Menu QVGA MB-Panels Setup Menu Parameters «Step by Step» ............4-1 4.1.1 Password ......................4-1 4.1.2 Title ......................... 4-2 4.1.3 Setup ......................4-3 4.1.4 System ......................4-4 4.1.5 Special (advanced function) ................4-5 4.1.6 Display ......................4-6 4.1.7 Keyboard/Barcode reader ................
  • Page 4 Content Saia-Burgess Controls AG 5.13 Firmware Download (MB-Panel side) ............. 5-21 5.13.1 FW Download by USB ..................5-21 5.13.2 FW Download by Ethernet ................5-22 5.14 Reboot MB-Panel ................... 5-22 Update & special settings Firmware Update .................... 6-1 Reset / Device Back to default parameters ............ 6-4 Contrast Adjustment ..................
  • Page 5 Content Saia-Burgess Controls AG Appendix QVGA and VGA MB-Panels Acoustic Alarm Introduction ..................... B-1 Using the uBT_AlarmStart container ............. B-4 VGA MB-Panel BacklightOn use Introduction ..................... C-1 Use of the uBT_BackLightOn container ............C-2 Haptic Effects Contact Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 6: Document History

    Content Saia-Burgess Controls AG Document History Date Version Changes Remarks EN00 2007-02-01 Initial Edition EN00 2007-03-02 Replaced pictures from CPUs with actual Design EN00 2007-04-02 5.6.1 Replaced Word table with trough InDesign table EN01 2007-06-27 New chapter EN01 2007-09-13 1.5.9 Numericpad.teq replaced with keypad.teq EN02 2007-11-26 Update based on FW1.08.00...
  • Page 7: Quickstart 1.1 Introduction

    PCD controllers include simple, built-in protec- tion features. However, secure operation on the internet is only ensured if exter- nal routers are used with a firewall and encrypted VPN connections. For more information, please refer to our support site: www.sbc-support.com/security Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 8: Connectors Definition

    Quickstart Saia-Burgess Controls AG Connector definition | Power supply 1.2 Connectors definition RS-485 RS-232 X1 = USB connector as Service Port X2 = Ethernet RJ-45 connector as main/fast communication X3 = RS-232 D-SUB 9 poles connector as printer output or S-Bus communication X4 = PS/2 MiniDIN 6 poles connector as Keyboard/Barcode reader input X5 = RS-485/Power spring connector as S-BUS comm. / Power input 24 V Power supply Connection Connector X5...
  • Page 9: Dimension And Cut-Out (All In Mm)

    Quickstart Saia-Burgess Controls AG Dimension and cut-out Dimension and cut-out (all in mm) PCD7.D435xxxx, und PCD7.D457xxxx Front panel W × H: 202 × 156 Cut-out W × H: 189 × 142 Display 5.7“ W × H: 117 × 88 Display 3.5“ W × H: 73 × 56 PCD7.D410VTCF Front panel W ×...
  • Page 10: Installation Of The Mounting Brackets

    Quickstart Saia-Burgess Controls AG Installation of the mounting brackets Installation of the mounting brackets ■ Mounting position is horizontal. CUT-OUT dimension : 189 × 142 mm or 262 × 202 mm ■ Slide the unit into the cut out hole ■...
  • Page 11: Operation And Handling

    Quickstart Saia-Burgess Controls AG Operation and handling Operation and handling 1.6.1 Base Line 5.7" MB-Panels and 10.4" MB-Panel Touch-screen operated by finger or pen (stylus). Do not operate with sharp tools (e.g. screw drivers) 1.6.2 Comfort Line MB-Panels (combined touch and keypad) ■ Functions F1 to F6 → directly with F key depression. ■...
  • Page 12: Communication

    ■ At the beginning the Saia PCD used must have a Web program loaded in it, cre- ated with the Web-Editor (see manual 26-838_Manual_Web-Editor). Some exam- ples can be asked to our SBC Support Team or soon available on our Internet site. CAT5 cross cable ■...
  • Page 13: Serial S-Bus Communication Over Rs-485

    (shielded is always better). ■ On the side PCD1.M125 you can plug your cable onto one of the serial RS-485 port at disposal using for ex. the port #1 (together with PCD7.F110 Module). ■ Then define the HW settings of the Saia PCD device (see PG5: SBC Project Man- ager). S-Bus support must be selected. Enter a valid Station Number. Serial S-Bus Port must also be activated and configured as the following example: Setup adjustment of MB-Panel: Configure now the MB-Panel entering in the Setup Menu (refer to chapters 5 and 6): ...
  • Page 14  You can now adjust the SBus connection settings and define the name, type and Station Nr you want to access to. Be sure you saved your definition. Now, if your SBC PLC is also well set up, you should be able to get a check mark  beside your connection settings. This means you are connected to the Saia PCD, but you still have to type the right Name of Start Page in the Menu Configuration (as shown in the Menu SBus connection settings, ex.
  • Page 15: Serial S-Bus Communication Over Rs-232

    PCD7.D4xx. Have a 3-wire cable (shielded is always better). ■ On the side PCD2.M150 you can plug your cable onto one of the serial RS-232 port at disposal using for ex. the port #1 (together with PCD7.F120 Module). ■ Then define the HW settings of the Saia PCD device (see PG5: SBC Project Man- ager). S-Bus support must be selected. Enter a valid Station Number. Serial S-Bus Port must also be activated and configured as the following example: Setup adjustment: Configure now the MB-Panel entering in the Setup Menu (refer to chapters 5 and 6): ...
  • Page 16 Saia-Burgess Controls AG Communication check mark  Now, if your SBC PLC is also well set up, you should be able to get a beside your connection settings. This means you are connected to the SBC PLC, Name of Start Page but you still have to type the right in the Menu Configuration (as shown in the Menu SBus connection settings, ex.
  • Page 17: Transparent Communication Tcp To Rs-232 (Ex. Printer Port) (Only With Qvga-Panels)

    Quickstart Saia-Burgess Controls AG Communication 1.7.4 Transparent communication TCP to RS-232 (ex. printer port) (only with QVGA-Panels) The goal of this communication is to send information from the EthernetPort «directly» to the RS-232 port. Why? This is an option provided to customers who want to connect a printer directly on the MB-Panel, receiving the Information packet from the PLC connected to (over the Ethernet port).
  • Page 18: Ether-S-Bus Communication On Ethernet Port

    Quickstart Saia-Burgess Controls AG Communication 1.7.5 Ether-S-Bus Communication on Ethernet Port Depending on the application you set up, you may like to use the Protocol Ether-S- Bus together with a PLC (see HW system overview for Saia PCD type allowed) This Ether-S-Bus connection is foreseen to be used between our PCD7.D4xx and PCD3.M3/M5, PCD1.M135+F650, PCD2.M150/M170+F650 or PCD2.M480/7+F650 where «less fast»...
  • Page 19: Profi-S-Net Communication On Rs-485 (Port #1)

    Quickstart Saia-Burgess Controls AG Communication Now your MB-Panel should be connected to the Saia PCD and the start page select- ed should be displayed on the screen. You can now navigate in your Web-pages ! 1.7.6 Profi-S-Net Communication on RS-485 (Port #1) This protocol is in preparation. This protocol is only on PCD3.M3/M5 at the speed of 187.5 Kbit/s. 1-13 Manual PCD7.D4xx │ ...
  • Page 20: Ps/2 Port For Keyboard Or Barcode Reader

    Quickstart Saia-Burgess Controls AG Communication 1.7.7 PS/2 Port for Keyboard or Barcode reader Attach any PS/2 Device like a Keyboard or Barcode reader to this port and read back its content in a field, register or variable its content. X4 - PS/2 Any Comm. The only thing you have to do is configure which keyboard country type or Barcode reader you have at disposal. For this, just go in the Setup Menu below Keyboard and choose one of the following PS/2 Keyboard Layout in the list box.
  • Page 21: Usb Port As Service Port

    This port commonly called the service port has multiple functions. Its main use serves to make download of new FW program. Another use consists to access the internal data for analyses. Future development regarding download of SBC-Web pages is under consideration but no release date is actually planned. 1.7.9 Get Started with Web-Editor on MicroBrowser Panel PCD7.D4xx...
  • Page 22: Hardware-System Overview

    Hardware-System Overview Saia-Burgess Controls AG Product Range Hardware-System Overview Product Range The range of MB-Panel (Micro-Browser Panel), named PCD7.D4xx, contains different Web-Panel between LCD size 3.5" and 10.4" that is adapted to the Saia PCD range. They have been developed for building automation and industrial applications. In combination with the program Web-Editor, an add-on tool of the Saia PG5 program- ming package, they provide a simple way of displaying Web pages easily created with our Web-Editor SW.
  • Page 23: Vga Mb-Panels

    Hardware-System Overview Saia-Burgess Controls AG Product Range 2.1.2 VGA MB-Panels Base Line MB-Panel 5.7": Including Touchscreen, communication Ethernet RJ-45, S-Bus RS-232/485, USB client Type PCD7.D457VTCF  Panel with LCD size 5.7" , color TFT and VGA resolution, white LED backlight. Type PCD7.D457VTCFH ...
  • Page 24: Hardware Pcb Bloc View

    Hardware-System Overview Saia-Burgess Controls AG Hardware PCB Bloc view | Custom/OEM Range Hardware PCB Bloc view Custom/OEM Range Different OEM Model can be asked using the same HW Base Platform. Below are two examples: For each standard type, a polyester foil with the type and the Saia Burgess Controls logo covers the whole front side.
  • Page 25: Technical Data

    262 × 202 Accessories Kits for In-Wall mounting PCD7.D457-IWS Kits for on-Wall mounting PCD7.D457-0WS 1) http direct  /   E ther-S-Bus 4) Serial-S-Bus 2) Serial-S-Bus 5) available without SBC Logo 3) Serial-S-Bus and printer Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 26: Interface Connection

    Hardware-System Overview Saia-Burgess Controls AG Interface connection Interface connection 2.5.1 Ethernet port RJ-45, X2 Connection between terminal PCD7.D4xx and PCD1.M135, PCD2.M150, PCD2.M170 and PCD2.M480 can be made. You can use a Standard or CAT5 «crossed» Ethernet cable equally when using the X2 Port in http direct or Ether-S-Bus. To multiple the network connections, please use Fast Ethernet Switch 10/100 Mbps resp.
  • Page 27: S-Bus On Rs-485

    Hardware-System Overview Saia-Burgess Controls AG Interface connection 2.5.2 S-Bus on RS-485 PCD7.D4xx PCD3.M3/M5 PCD1:M125/135 PCD2.M150/M170/M480 Port #2 or 1 with PCD3.F110/F150 Port #1 Port #1 with PCD7.F110/F150 or Port 6 (M480) RS-485 Network connection Pining nr of each PLC connected is defined in their dedicated manual. Termination resistors for proper End of line In the example below, you see a possible interconnection between terminals and PLCs. In order to avoid reflexions on the communication line please terminate the network with termination resistors.
  • Page 28: Ps/2 Interface

    Hardware-System Overview Saia-Burgess Controls AG Interface connection 2.5.3 S-Bus on RS-232 PCD7.D4xx PCD3.M3/M5 PCD1:M125/135 PCD2.M150/M170/M480 Port #0 or 1 with PCD3.F121 Port #0 or 1 with PCD7.F120 Port #0 or 1 with PCD7.F120+F121(M480) RS-232 Point to point comm. Interface pining: 2.5.4 PS/2 Interface This interface uses a standard MiniDIN connector 6-pin as follow : Pin 1: PS2/Data Pin 2,6: n.c. Pin 3: Pin 4: +5 V Pin 5: PS2/Clock What can we connect to? Instead of using the virtual Keyboard from the MB-Panel, you can use this interface to...
  • Page 29: Communication Mode Setting

    Communication mode settings Saia-Burgess Controls AG Baudrate and Controls - Http direct | Ether S-Bus Communication mode setting Http direct – Baudrate and Controls On this communication port, there is an autonegociation mode between the MB-Pan- el and the Ethernet switch or the PLC directly attached to. This mode will defined him- self the speed rate 10 Mbps or 100 Mbps. For sure the max speed rate at 100 Mbps is better.
  • Page 30: S-Bus - Baudrate And Controls

    Communication mode settings Saia-Burgess Controls AG S-Bus | Printer port TCP to RS232 | PS/2 port | USB port S-Bus – Baudrate and Controls Here the user must defined himself the communication speed he wants to setup. For this, you must adjust the Baudrate in the Setup Menu/Configuration/Communication Port #0 or 1 - Configure : Possible Baudrate : 1200, 2400, 4800, 9600, 19'200, 38'400, 57'600, 115'200 bps Please ask our support to help you set-up the more efficient communication speed in your network configuration. It can be sometimes useful to reduce the baudrate in order to save the PLC ressources for other applications. Other parameter cab also be set like TN Delay, TS Delay,Timeout or Retries. Printer port TCP to RS-232 (TCP2RS-232) –...
  • Page 31: Setup Menu Qvga Mb-Panels

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» Setup Menu QVGA MB-Panels Setup Menu Parameters «Step by Step» ■ This chapter describes the «Menu structure» of the QVGA eMicroBrowser Panels, based on FW Version 1.10.45 minimum. ■...
  • Page 32: Title

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.2 Title Appears after some seconds. This time is defined in the setup page «System». Titlestring Default «uB Terminal». Can be changed in «System». Firmware Version Firmware version (read only) Access to Setup Menu Press «Enter Setup» to enter to main setup menu. Manual PCD7.D4xx │ ...
  • Page 33: Setup

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.3 Setup Network Settings of the MB-Panel Display Display settings Keyboard PS/2 keyboard setting Password Enter a password Configuration Address and name of the start page System System info + download FW Stylus Re-calibration...
  • Page 34: System

    System Firmware version V xxxx Firmware version (read only) Booter version V xxx Booter version (read only) Configuration Default: SBC standard Read only Serial Nr. xxxxxxxxxx Serial Number: This number is unique! It can be used for product traceability Title Default: uB Terminal This string is displayed on the title page (...
  • Page 35: Special (Advanced Function)

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.5 Special (advanced function) Setup timeout (s) Default: 10 seconds The title page is displayed for this amount of time. Minimum: 3 sec- If set at «0», the title page will not be called. onds Format Default status...
  • Page 36: Display

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.6 Display Contrast default: 10 Adjustment between 0 to 21 by pressing on – and + buttons Backlight default: The backlight turns off if neither the touch-screen nor any keys timeout (min) 15 min.
  • Page 37: Keyboard/Barcode Reader

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.7 Keyboard/Barcode reader For external keyboard or barcode reader. (Mini Din 6 with standard pin-assignment) PS/2 keyboard Layout Default: GE (German) Keyboard languages : ● GE (German) ● US (English US) ●...
  • Page 38: Password

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.8 Password  Forgot your password? See chapter 5 «Enter Password» Password Default: no password Only numerical Save and Back to the main setup menu  Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 39: 4.1.9 Network

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» 4.1.9 Network MAC address As information For information ( read only) TCP/IP Address Default: 127.0.0.1 IP address of the MB-Panel Subnet mask Default: 255.255.255.0 Default gateway Default: 0.0.0.0 Save and return to main setup menu ...
  • Page 40: Setup Menu Configuration "Step By Step

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2 Setup Menu Configuration «step by step» 4.2.1 Configuration Address of the start page Default:127.0.0.1 (Proxy address) IP address of the Saia PCD Name of the start page Default:Start.html html page generated by the web editor project Special Advanced configuration Communication S-Bus / Ether-S-Bus communication SD-card Appear only if SD-card is installed Back to configuration menu...
  • Page 41: Special

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.2 Special File cache Default: Ena- The file cache can be enabled/disabled. bled Disabling is only useful for projects in develop- In normal op- ment, in order to see the visible change in files eration, the file cached. cache should always be ena- bled. Local & remote Default: «No local file search» means that no files server «no local file...
  • Page 42 Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4-12 Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 43: Communication

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.3 Communication Port #0 Default: Port #0 (D-sub 9) (RS-232) SBUS - None: no S-Bus communication - SBUS: Communication Serial S-Bus RS- - TCP2RS232 :TCP/IP to RS-232. Using MB-Panel as gateway ( for example for Printer output) Configure Port #0 - S-Bus configuration on Port #0 - Configuration of TCP2RS232 on Port 0 (TCP2RS232 means TCP to RS-232)
  • Page 44: 4.2.4 Configuration Port #0 (Rs-232) Serial S-Bus

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.4 Configuration Port #0 (RS-232) Serial S-Bus Baudrate Default: 9600 Adjustment: from 1200 to 115'200 TN Delay (ms) Default: 0 TS Delay (ms) Default: 0 Timeout (ms) Default and standard: 250 S-Bus configuration Retries Default: 3 Number of attempts: try + retries Back to communication menu ...
  • Page 45: 4.2.5 Configuration Port #1 (Rs-485) Serial S-Bus

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.5 Configuration Port #1 (RS-485) Serial S-Bus Baudrate Default: 9600 Adjustment: from 1200 to 115'200 TN Delay (ms) Default: 0 S-Bus configuration TS Delay (ms) Default: 0 S-Bus configuration Timeout (ms) Default and standard: 250 S-Bus configuration Retries Default: 3 Number of attempts: try + retries Back to communication menu ...
  • Page 46: Ether S-Bus Configuration

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.6 Ether S-Bus Configuration Timeout (ms) Default and standard: 250 S-Bus configuration Retries Default: 3 Number of attempts: try + retries Back to communication menu  4-16 Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 47: S-Bus Connection

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.7 S-Bus Connection This page lets you defining 16 S-Bus different S-Bus connections resp. stations S-Bus name Default: none Entering all connection setting of each station: S-Bus communication status Default: none Status of communication  = communication OK – = communication error Back to communication menu ...
  • Page 48: S-Bus Connection Settings

    Setup Menu QVGA MB-Panels Saia-Burgess Controls AG Setup Menu Configuration “step by step” 4.2.8 S-Bus Connection Settings  Potential source of communication error List of error reasons: - Bad cabling. Most common error. - Bad grounding. Can cause damage to the interface! - Connection to the wrong serial line. - Incompatible transmission speed.
  • Page 49: Option, Sd-Card Memory Pcd7.Rd4-Sd

    Backup: Copy content of «M1_FLASH/WEBPAGES» onto SD_Card  Copy or (.SAR format archive file) or restore content of backup archive  restore file to «M1_FLASH/WEBPAGES» Condition: /webpages must be not empty Archive name Name: 20 characters max with no spaces or spec. charact. Cloning and backup files are the same extension format: .SAR (SBC Archiv) Back to the configuration menu  4-19 Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 50 Restoring choose in the lists FTP access to cloning and backup folders SLOFLASH Backupfolder Clonefolder BE CAREFULL! case sensitive SBC filesystem does not support file names in ANSI characters but only ASCII char- acters (code 0 to 127). The names of .teq, itq, html .gif .bft and .csv files, which should be copy in the M1_ FLASH or SLOFLASH, must be write with ASCII characters without spaces and the maximum number of characters (extension figure included) is 24. 4-20...
  • Page 51: Setup Menu Vga Mb-Panels

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Setup Menu Parameters «Step by Step» | Setup Menu Setup Menu VGA MB-Panels Setup Menu Parameters «Step by Step» ■ This chapter describes the Menu structure of the VGA eMicrobrowser Panels, based on the FW version 1.12.11 minimum for PCD7.D457 VTCF, D457 VMCF, D410 VTCF and FW 1.12.15 minimum for PCD7.D457 VTCFH.
  • Page 52: Password

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Password | Save and quit | SETUP screen Password MB-Panels from the PCD7.D4xxx series are delivered without a Setup password. However, if a password has subsequently been defined for access to the Setup menu, you will have to enter the correct password and confirm it with OK. Save and quit By changing one or several parameters, you must confirm that you want to save, save & reboot or not save the new parameters. SETUP screen Setup screen is the first screen that appears by entering in the setup menu. Network MB-Panel settings Web connection Configuration of the Web connection System...
  • Page 53: Network

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Network | Web connection 5.6 Network Mac Adress Read only For information TCP/IP Address Read/write IP address of the MB-Panel Subnet Mask Read/write Subnet Mask IP address Default gateway Read/write Default gateway IP address Setup Return the main setup menu Web connection Start page Default start page name of the web project...
  • Page 54: Type Of Connection

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Web connection 5.7.1 TYPE of connection Local No connection with any Saia PCD The connection is to the local IP address 127.0.0.1 Httpdirect http direct connection (Ethernet only) S-Bus S-Bus connection (serial or Ethernet) Edit web connection Return to the web connection 5.7.2 Parameters of a Httpdirect connection For external keyboard or barcode reader. (Mini DIN 6 with standard pin-assignment)
  • Page 55: Type Of S-Bus Interface Connection

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Web connection 5.7.3 Type of S-Bus Interface connection Ethernet Ether-S-Bus connection Serial port 0 Serial S-Bus connection Port 0 RS-232 (D-Sub 9) Serial port 1 Serial S-Bus connection Port 1 RS-485 (orange spring connector no.1,2,3) Parameter Return to parameter menu 5.7.4...
  • Page 56: Parameters Of Serial S-Bus Connection

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Web connection 5.7.5 Parameters of Serial S-Bus connection Type S-Bus Read only Interface Serial Port 0 (or 1) Serial S-Bus connection Remote S-Bus Address 1 ( default) Up to 253 S-Bus address of the Saia PCD Baudrate 9600 KBits/s (default) Selection of the conmunication...
  • Page 57: System

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG System System 1 Info System info (FW , booter versions…) 2 Settings Concern: buzzer, order of file search, startup timeout, infoscreen, file cache, autorepeat. 3 Special Reset parameters, format M1_flash and Intflash. 4 Log Overview log.txt 5 FW Download Select mode of downloading 6 Reboot Reboot MB panels (with confirmation). Like a power OFF and ON, but without any HW switching 7 Setup Return the main setup menu Manual PCD7.D4xx │ ...
  • Page 58: System Info

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG System 5.8.1 System info Firmware version V xxxxxxx Firmware version of the MB-Panel (Read only) Booter version V xxxxxxx Booter version of the MB-Panel (Read only) Special config Customising product (Read only) Serial number xx.xx .
  • Page 59: Settings

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG System 5.8.2 Settings Buzzer On / Off / frequency Order of file search Local / remote files Delay during Startup (s) 4 (default) Min: 0 & Max:15 Intro screen Entry welcome text and splash image File Cache enabled Default: Enabled The file cache can be enabled/ disabled.
  • Page 60: Buzzer

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG System 5.8.3 Buzzer Buzzer on/off Default is on Change by pressing once Buzzer Frequency Default is 1000 Select between 125 and 8000 Hz System Return to system page 5-10 Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 61: Order Of File Search

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Order of file search 5.9 Order of file search No local file search Default «No local file search» means that no files (.teq or .gif) will be searched in the local server (= uBrowser server). Local before «Local file search before remote» means that files (.teq or remote .gif) will be searched in the local server before searching in the PLC server. With additional SD-card, files will be searched first in M1_ FLASH (embedded 4MB flash), then in SLOFLASH (SD-card flash).
  • Page 62: Intro Screen

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Order of file search 5.9.1 Intro screen Welcome text Default: Welcome Free welcome text X position of text Default X= 400 pixel Value between 0 and 639 Y position of text Default Y= 300 pixel Value between 0 and 479 Filename of Graphic SBCSUGrande.gif Gif file...
  • Page 63: System Special (Advanced And Haptic)

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Order of file search 5.9.2 System Special (advanced and haptic)  Only for Haptic MB panel VTCFH Warning! S-Bus on Port 0 will not work if haptic is enabled - see the section 5.9.2.1 Reset all parameters This command allows to reset all parameters to the default values Format M1_FLASH file Advanced function with this message of confirmation: «Do you really...
  • Page 64 Setup Menu VGA MB-Panels Saia-Burgess Controls AG Order of file search • Effect 0 – no effect • Effect 1 – 6: Various clicks to simulate button presses • Effect 7 – 9: Various buzzes to simulate alarms • Effect 10 – 15: Effects gradually increasing in amplitude and duration •...
  • Page 65: Log

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Order of file search 5.9.3   LOG.TXT/Read only Glance over the list by pressing on the touch. That allows controlling, for example, if the fonts are found. At the back page: Info regarding the errors. Access to log.txt via FTP: uBT_FS/LOG.TXT System Return to the system menu...
  • Page 66: Display

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Display 5.10 Display Dimming Default: 10 Adjustable between 0 and 20 Backlight timeout (min) Default: 15 The backlight turns off if neither the touch- minutes screen nor any keys are pressed during this time.
  • Page 67: 5.10.1 Rotation

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Display 5.10.1 Rotation 0°, 90°, 180°, 270° Defualt: 0° Change the orientation landscape to portrait and inverted Display Return to display menu 5.10.2 Resolution Auto Default The panel tries to determine the resolution of each teq. All teq’s are displayed with VGA resolution QVGA All teq’s are displayed with QVGA resolution...
  • Page 68: Keyboard

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Keyboard 5.11 Keyboard Build-in keyboard layout PS/2 keyboard layout Default: GE (German) PS/2 External Keyboard languages GE (German) or US (English US) or UK (Eng- lish UK) or FR (French) CH-GE (Swiss German) or CH-FR (Swiss French) SIP (virtual keyboard) Default: Enabled Enable/Disable SIP (Soft Input Panel).
  • Page 69: 5.11.1 Build-In Keyboard Layout

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Keyboard 5.11.1 Build-in keyboard layout Comfort line Keyboard layout VGA MB panel with keys/Fkeys Handheld VGA Keyboard layout VGA Handheld. Handheld QVGA Keyboard layout QVGA Handheld. (old version) OEM 1 Customer specific Keyboard Return to the keyboard menu 5-19 Manual PCD7.D4xx │ ...
  • Page 70: Enter Password

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Enter Password 5.12 Enter Password Setting a password Alpha, numeric or alphanumeric password is possible (maximum characters = 32 , spaces included) If setting a password, a confirmation is required. If setting a new password, a confirmation is required and if the entered phrases do no match, the old password is retained. If you want to remove password protection, just enter and confirm no characters  Forgot your password  delete the passwd.dat file (FTP connexion) it’s all 5-20 Manual PCD7.D4xx │ ...
  • Page 71: Firmware Download (Mb-Panel Side)

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Firmware Download 5.13 Firmware Download (MB-Panel side) 1 Download by using USB 2 Download by using Ethernet 3 System Return to system page 5.13.1 FW Download by USB 1 Download by using USB Hit the download button to put the MB-Panel into download mode.
  • Page 72: 5.13.2 Fw Download By Ethernet

    Setup Menu VGA MB-Panels Saia-Burgess Controls AG Reboot MB-Panel 5.13.2 FW Download by Ethernet 1 TCP/IP address Read only 2 Subnet Mask Read only 3 S-Bus station Read/write You may change the S-Bus station number before hitting the download to put the MB-Panel into download mode. After a successful update of the FW, the MB-Panel will restart automatically.
  • Page 73: Update & Special Settings

    USB cable on the MB-Panel and connect it to a PC or Laptop where our FW Download tool is recorded. A SBC based Saia PG5 SW-tool is provided. You can either start it through our Saia PG5 SW or with a FW Installer that you can find on our Internet Support page. For touch screen Comfort and base lines 5.7" and 10.4"...
  • Page 74 Update & special settings Saia-Burgess Controls AG Firmware Update If the connection is not written USB in PGU/Auto mode, go in menu File/online settings and adjust the connection to USB port as follow: Update von Booter file: Please only use our «Installer Package» as this operation is not common The best way to make the FW Download is to : 1. Start your FW download tool and configure it, as explained.
  • Page 75 Update & special settings Saia-Burgess Controls AG Firmware Update If the green LED doesn’t light as described, then do the following added step: A. Power off the MB-Panel B. O n the Top of the Back Cover there is a hole of 3 mm diameter. Inside you’ll find a button. Take a fine pen or a little screwdriver and press continously (hold it) on that reset button: button. Here below the position of that reset button C. T hen at the same time Power ON the MB-Panel. Wait about 3-4 sec. until the LED is flashing. Then go back to upper chapter 5.
  • Page 76: Reset / Device Back To Default Parameters

    Update & special settings Saia-Burgess Controls AG Reset | Contrast Adjustment Reset / Device Back to default parameters The reset button from previous chapter 6.0 can also be used in some special cases to make a full reset of the MB-Panel and to restore the default parameters set from the manufacturer.
  • Page 77: Backlight Control

    Update & special settings Saia-Burgess Controls AG Backlight Control Backlight Control This function helps you saving energy. When the Backlight is deactivated, you save about 3/4 Watts. That is not negligible. Not only, the Backlight lifetime is saved resp. increased. CCFL and LED backlight. According to the types of MB-Panels, the backlight technology is CCFL or LED Types Backlighting PCD7.D457BTCF...
  • Page 78: Recognized Fonts Of The Mb-Panel Pcd7.D4Xx

    Update & special settings Saia-Burgess Controls AG Recognized Fonts of the MB-Panel PCD7.D4xx Recognized Fonts of the MB-Panel PCD7.D4xx Supported basic fonts The user can put any font indication in the request code. The font can be pre-defined and supported by default, specially loaded, or not loaded at all. Also pre-defined fonts can be overloaded by other font definitions at wish. The pre-defined fonts are: Default fonts available for QVGA MB-Panels Font and font style Character Size Arial...
  • Page 79 Update & special settings Saia-Burgess Controls AG Recognized Fonts of the MB-Panel PCD7.D4xx The text field on the edit box is currently still written on the whole area and will be overwritten with the outline and 3D shading at outline use if chosen too big. The but- ton text field is written on the inside is correctly written within, as with the simple text box and (new for the firmware) multiline text box use. The added margins to be reckoned with are: •...
  • Page 80: Special Unicode Fonts

    Update & special settings Saia-Burgess Controls AG Special Unicode fonts Special Unicode fonts 6.6.1 General The user is able to provide additional fonts to satisfy his requirements regarding the languages he is using or regarding special fonts/style/size which are not standard in the MB-Panel.
  • Page 81: Multilanguages: Example

    Change a language by pressing on a button (set variable on mouse down) Basic example is a translation of Happy Birthday in «Czech» in using «HTML TAG» type. The «Czech» language needs extended European characters which are download- able from sbc-support site in restricted area. What’s the drill? 1) The Unicode Font(s).bft file(s) with extended European characters must be copied under … /FONT 2) Web-editor: Edit a static text with the text «Happy Birthday»...
  • Page 82 Update & special settings Saia-Burgess Controls AG Special Unicode fonts 4) Web-editor: create a button with the following «Actions Set variables» parameters: type is «container», name is «@LANGUAGE» them the Unicode .csv file. 5) Attention: Copy (by ftp) the Unicode .csv file (or files if several languages→as many languages as many ..csv files) under M1_flash/ Webpages/… Job done 6-10 Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 83: Interpretation Of Wrong Fonts (Types, Sizes Or Styles)

    Update & special settings Saia-Burgess Controls AG Special Unicode fonts 6.6.3 Interpretation of wrong fonts (types, sizes or styles) VGA Panel 1. Arial, same style,keep size 2. Arial, plain,keep size If this size does not exist for Arial : 3. Same font name, same style,reduce size to the next best 4.
  • Page 84: Web-Editor

    Update & special settings Saia-Burgess Controls AG Special Unicode fonts 6.6.4 Web-editor The Unicode character set ais available: ■ by using the source type «HTML tag» in the web editor and via a .CSV file. ■ by entering the text as a «string» directly in the web editor, in this case, it is not necessary to use .CSV files. In this case don’t import Web-Editor project which was compiled with a Microsoft Windows using Unicode characters set A to another Microsoft Windows using Unicode characters set B.) 6-12 Manual PCD7.D4xx │ ...
  • Page 85: Special Internal Functions

    Update & special settings Saia-Burgess Controls AG Special internal Functions Special internal Functions 6.7.1 Container variables for QVGA MB-Panels Container variables, available to the user, are included in the firmware of these termi- nals. Containers let the application program exchange information with the firmware. All container variables have the prefix «uBT_». Caution: case sensitive! Container Variable Description (source HN) Config option uBT_ Version Read Read only: Used firmware version only uBT_DispType Read The container is Not active only uBT_BooterVersion Read Read only: Used firmware booter version...
  • Page 86 Update & special settings Saia-Burgess Controls AG Special internal Functions Container Variable Description (source HN) Config option uBT_LocalFileSearch Read/Write 0→No local file search. Each file is loaded from the local cache or remote. Read/Write 1→Local file search with local before remote. Read/Write 2→Local file search with remote before local. At active cache a file will be loaded, if present, from the cache in all cases. A switch of these settings at run time may first be fully ef- fective after an URL jump and should be used with care. uBT_ DoLcdCalib If touchscreen is present Read/Write‚1’→a recalibration is executed.
  • Page 87 Update & special settings Saia-Burgess Controls AG Special internal Functions Container Variable Description (source HN) Config option uBT_EnableSIP Read/Write SIP→Select Soft Input Panel (keyboard on the screen) Write 0→SIP is disabled. Virtual keyboards are disabled. Write 1→SIP is enabled. Virtual keyboards (alphapad.teq and keypad.teq) are enabled. uBT_FirstPadName File name entry for an alternative virtual keyboard file as replacement for alphapad.teq at local file use. At local file use alphapad.teq from the setup menu (from INTFLASH/WEB) is used by default. The alternative file–that must be named otherwise than alphapad.teq–can be placed in M1 or SD flash over FTP, or included in the stored web project in the remote server. The maximum number of characters (file extension with dot included) is 24.
  • Page 88 Update & special settings Saia-Burgess Controls AG Special internal Functions To use FTP an Ethernet connection is required. Do not use write access on the container from the application and over FTP at the same time. This may lead to undefined results. ** Acoustic alarm: New feature for QVGA FW 1.10.45 upwards. Button and Edit pain ter use is supported. See also the Appendix B. 6-16 Manual PCD7.D4xx │ ...
  • Page 89: Container Variables For Vga Mb-Panels

    Update & special settings Saia-Burgess Controls AG Special internal Functions 6.7.2 Container variables for VGA MB-Panels Container variables, available to the user, are included in the firmware of these terminals. Containers let the application program exchange information with the firmware. All container variables have the prefix «uBT_». Be careful, these functions are «case sensitive» It might be that the version of this manual does not correspond with the Up-to-date version of the user’s guide which is the references document regarding this list of container variable.
  • Page 90 Update & special settings Saia-Burgess Controls AG Special internal Functions Config Container Type Default Description file (Source HN Value Value entry 10.03.10) Length Length uBT_Backlight Boolean Read/Write1, 0→Remote backlight value control OFF string The backlight is switched OFF if the control is ‘1’ before. Any touch on the screen switches the back- light on again.
  • Page 91 Update & special settings Saia-Burgess Controls AG Special internal Functions Config Container Type Default Description file (Source HN Value Value entry 10.03.10) Length Length uBT_BuzzVol Decimal 0 : OFF Read/write buzzer volume setting enumer- 100% (0…20). ated value This sets the volume of the acous- string tic signal at the use of the touch function of the touch panel.
  • Page 92 Update & special settings Saia-Burgess Controls AG Special internal Functions Config Container Type Default Description file (Source HN Value Value entry 10.03.10) Length Length uBT_EnableCache Boolean File cache use (1), 0 no file cache value (enabled) for all non-image visualization files. string Files first are cached the moment they are used. The cache is the place where files are searched first, independent of local file use settings. The cache is cleared at start-up and at URL jumps.
  • Page 93 Update & special settings Saia-Burgess Controls AG Special internal Functions Config Container Type Default Description file (Source HN Value Value entry 10.03.10) Length Length uBT_InactivityPoll- ANSI text Touch / Keyboard inactivaty super- Time string visory selection (1), at 0 off. Used for a switch to a less frequent touch / keyboard entry polling mode.
  • Page 94 Update & special settings Saia-Burgess Controls AG Special internal Functions Config Container Type Default Description file (Source HN Value Value entry 10.03.10) Length Length uBT_Local- Decimal Local before Select local filesearch mode FileSearch enumer- remote (1) 0: no local file use ated value 1: use local files before remote string 2: use remote files before local The local search order is fixed, in order of use: - Video cache (image only) - File cache (if enabled) - Internal Flash...
  • Page 95: Ubt_Backlight Container Diagram

    Update & special settings Saia-Burgess Controls AG Special internal Functions 6.7.3 uBT_BackLight container diagram 6.7.4 Additional uBTerminal containers for «Haptic» panel Container variables, available to the user, are included in the firmware of these termi- nals. Containers let the application program exchange information with the firmware. All container variables have the prefix «uBT_». Caution: case sensitive! Container names Range Default Description access uBT_HapticOn Careful: Never change (in all case) the default value (1) of this container. uBT_HapticEnable 0 or 1 If set to 1, haptic effects are enabled.
  • Page 96: Function Keys Access

    Update & special settings Saia-Burgess Controls AG Special internal Functions 6.7.5 Function KEYS Access When you have Function Keys on your Panel (Comfort line version), you can define which action you want to give to your F-Keys HOW to program these in the Web-Editor Project? A. Open a *.teq page As normally this F-Keys should be reached every time, like the Help or the Back Home functions, it makes sense to place these F-Keys in the file «background.teq»...
  • Page 97: Special Internal Functions

    Update & special settings Saia-Burgess Controls AG Special internal Functions Special internal Functions An internal serial Flash is always equipped. Its capacity is defined at 4 MBytes. Goal of this added memory? When you use slow communication speed, the transfer of data takes time from the PLC to the MB-Panel. A possibility consist of loading locally the project files *.teq and *.gif, created for the Web-Server in PLC, using this internal 4 MBytes memory flash. How to access the files locally in the internal memory? Different art to access these files can be defined in the Setup Menu Configuration/ Advanced.
  • Page 98: Ftp Connection

    Update & special settings Saia-Burgess Controls AG FTP connection FTP connection You can access internal Memory system making a FTP connection PC to MB-Panel using the TCP/IP Address set in the Panel. BE CAREFUL: you can destroy some data and then loose the control of your panel if you erase some important files.
  • Page 99: List Of Message-Box Messages

    Update & special settings Saia-Burgess Controls AG List of Message-Box messages 6.10 List of Message-Box messages Messages Remarks Out of memory in Ramdisk May appear if a file (most commonly a .gif) is too large. VGA MB panel: < 256 Kb (see also section 6.11) Language Failed to parse .csv No memory is available to parse a .csv file. LR: out of memory or out of memory for No memory is available to parse a .csv file. or the total size language resource...
  • Page 100 Update & special settings Saia-Burgess Controls AG List of Message-Box messages Painter FV: buffer OVF in readln()! Probably the number of characters in a Multline object has been exceeded, This message can appear in two cases: 1) Case one is regarding the .csv file If one entry (line) of a .csv file is bigger than 128 bytes Info one: If .csv file is in ASCII code (1 byte per character) total entry (line) 128 characters If .csv file is in Unicode/UTF-16 (2 bytes per character)
  • Page 101: Error Messages Advanced For The Vga Mb Pannel

    Update & special settings Saia-Burgess Controls AG Error messages advanced for the VGA MB Pannel 6.11 Error messages advanced for the VGA MB Pannel Advanced: These following messages * can appear: If size memories used by the gif files, the painters, the html tags and containers var, the online trending and HD log, the language resources (.csv files) are too big. Some uBT_parameters must be adapted by changing values in the file uBTeminall.txt under :/INTFLASH/CONFIG/ (and over a ftp connection) After modification the Panel has to be restart. Recommendations: We advise not to have the maximum value in first time and try with the medium value because if we increased all the memories to max. values it might create big problems and decrease significantly the performances.
  • Page 102: Handling

    Handling Saia-Burgess Controls AG Touchscreen Glas | Temperature | Fix the Panel Handling Touchscreen Glas As the touchscreen is a type resistive, you can start an event by pressing on the screen with a finger or with any pen. BUT don’t use any sharpen edge pen otherwise the Touchscreen could be definitely damage!! The pressure to activate an event is predefined and not adjustable. When press- ing on the touchscreen (or on any membrane key), the buzzer is directly and shortly switch on (if volume is not 0).
  • Page 103: Information About Lcds Used In The Mb-Panel Display

    Handling Saia-Burgess Controls AG Information about LCDs used in the MB-Panel Display Information about LCDs used in the MB-Panel Display Precautions ■ The liquid inside the LCD contains an irritant. If some of this liquid makes contact with your skin, immediately wash the affected area with running water for a mini- mum of 15 minutes. ■ If the liquid from inside the LCD gets into your eyes, rinse your eyes with running water for 15 minutes and then consult a doctor.
  • Page 104: Maintenance

    Maintenance Saia-Burgess Controls AG Care Maintenance Care These panels have been designed for maintenance-free continuous operation. Recommendations for cleaning the front layer of the MB-Panels. The use of abrasive cleaners and/or cleaning implements that may damage or scratch the front layer should be avoided ! ■ Use denatured alcohol and apply it with a clean soft rag.
  • Page 105: Drywall Mounting Set For Mb-Panels

    Drywall mounting set Saia-Burgess Controls AG Drywall mounting set Drywall mounting set for MB-Panels The microbrowser panels are not just for mounting in the control cabinet: they also look very good in the office or living-room, or mounted on a wall. We recommend you to use the PCD7.D457VTCF (VGA) instead of the QVGA for the following reasons: ■ Access to the Setup menu without switch OFF then ON the panel ■ Firmware download over Ethernet...
  • Page 106: General Recommendations

    ● IMasterSBC5_xx_xx.jar is not necessary to display web page on a MB panel ● A t the minimum the .tcr file is the only one file which must be builded in the web server project (.wsp), all the other file of the project can be copied in the flash (PLC or local M1_flash of the MB panel) under Mx_flash/webpages/ ● g if file < 150 Kbytes and if possible < 320 and < 240 pixel (one pixel free around) ● a dd Unicode fonts→check in the list: http://www.sbc-support.com→them Prod- uct info→HMI→Web-Panel PCD7.D4xxx→ Additional information for Sales Companies (restricted Area) ● Y ou don’t find the right font in the list→Contact the Saia PCD support in Murten. We are willing to help you ● Maximum of objects (painters) by page is 256 (512 for VGA panels) ● F unction «Scalable» Project configuration→scalable html: Define HTMLs that resize the HMI during runtime according to a defined factor. Scale your HMI up to 200% for example without need to change your TEQ-Views. MicroBrowser will resize the TEQ-Views at runtime if you type in the URL of your new «scal-...
  • Page 107: 10.1.1 Recommendations For File And Path

    ● A dvanced: use the right tool to process to a hardware reset. Don’t use a paper clip or a needle. Use a drill Ø 3 and press softly on the microswitch. 10.1.1 Recommendations for file and path SBC filesystem does not support file names in ANSI characters but only ASCII char- acters (code 0 to 127). The names of .teq, itq, html .gif .bft and .csv files, which should be copy in the M1_ FLASH or SLOFLASH, must be write with ASCII characters without spaces and the maximum number of characters (extension figure included) is 24.
  • Page 108: Recommendations For Vga Panels

    ● I MasterSBC5_xx_xx.jar is not necessary to display web page on a MB panel ● A t the minimum the .tcr file is the only one file which must be builded in the web server project (.wsp), all the other file of the project can be copied in the flash (PLC or local M1_flash of the MB panel) under Mx_flash/webpages/ ● g if file <250 Kbytes and max 638 x 478 pixel (one pixel free around) ● a dd Unicode fonts→check in the list: http://www.sbc-support.com →them Prod- uct info→ HMI→Web-Panel PCD7.D4xxx→Additional information for Sales Companies (restricted Area) ● Y ou don’t find the right font in the list→Contact the Saia PCD support in Murten. We are willing to help you ● M B VGA panels don’t support yet «Online trends macros» (they are not correct time stamp) ● C alculation of the memory requirement see the section ...
  • Page 109: 10.2.1 Error Messages Advanced For The Vga Mb Pannel

    General recommendations Saia-Burgess Controls AG Recommendations for VGA panels Handling ● T ouch screen: the basic material of the touch screen is the glass. Don’t use screwdriver or hard tool to touch the touch. Touch only with the finger or a spe- cial «touch pen stylus» ● K ey-pads (for comfort line) : the tactile sensation being obtained by pressing a metal dome 12 mm. Don’t use screwdriver or hard tool to press on it. Press the key-pads only with the finger ● A dvanced: use the right tool to process to a hardware reset. Don’t use a paper clip or a needle.
  • Page 110: Alarming Macros Advanced

    General recommendations Saia-Burgess Controls AG Alarming Macros Advanced 10.3 Alarming Macros Advanced How changing the width of the columns of the alarm list? Example with the «Q_MacrAlarmingDefonline» Clic on the macro and select the Cross reference Tab then the Following STRING The widths of each columns were optimized according to the size of the screen and the number of pixel (QVGA = 240).
  • Page 111: A Appendix

    Appendix A Saia-Burgess Controls AG Icons Appendix Icons In manuals, this symbol refers the reader to further information in this manual or other manuals or technical information documents. As a rule there is no direct link to such documents. This symbol warns the reader of the risk to components from electrostatic discharges caused by touch.
  • Page 112: Introduction

    Appendix B Saia-Burgess Controls AG Introduction QVGA and VGA MB-Panels Acoustic Alarm Introduction Added to the configurable ‘beeper’ feature that is used as acoustic confirmation for touch screen activation, a special pulsed acoustic alarm option has been added. For acoustic alarm indication the following three containers have been added: Config Container Type Default Min.
  • Page 113 Appendix B Saia-Burgess Controls AG Introduction Alarm Volume parameter The alarm volume parameter sets the duty cycle of the pulsed alarm signal. At 0% it’s off, at 100% it is continuously on (no pulsing). The setting is used the moment the alarm is switched on.
  • Page 114 Appendix B Saia-Burgess Controls AG Introduction Note: If on the same view the macro «wr_PPO2CO-on_Repaint» is used the preceding button use will be (near) ineffective as at each repaint the PPO value will be taken and override it again. Example with in this case Register «PalarmInterval» (Symbol to be defined in the Saia PG5 symbol editor as global) (Remark also: Use Search / Update in this screen to define it and the PPO Initializa- tion button to define the type as DEC):...
  • Page 115: Using The Ubt_Alarmstart Container

    Appendix B Saia-Burgess Controls AG Using the uBT_AlarmStart container Using the uBT_AlarmStart container Writing to the uBT_AlarmStart container is handled as follows Writing value. At acoustic Alarm off At acoustic Alarm on At acoustic Alarm on with FW Version with FW Version later 1.08.52 QVGA than 1.08.52 on the (First release)
  • Page 116: Cvga Mb-Panel Backlighton Use Introduction

    Appendix C Saia-Burgess Controls AG Introduction VGA MB-Panel BacklightOn use Introduction The PCD7D4xx VGA Terminal allows the use of adjustable «BackLightOn». The following is supported: ● Back light intensity setting in 20 steps using the contrast setting in the setup menu. This includes full dark to maximum intensity setting ●...
  • Page 117: Use Of The Ubt_Backlighton Container

    Appendix C Saia-Burgess Controls AG Use of the uBT_BackLightOn container Use of the uBT_BackLightOn container uBT_BackLightOn container use in buttons The container can be used on a button using the set action option. Examples with screen on: ● Down off only (set to 0): The screen will go black at the touch down at stay black at the release.
  • Page 118 Appendix C Saia-Burgess Controls AG Use of the uBT_BackLightOn container Using the PPO to Container Macro for the uBT_BackLightOn control the following is found: ● Writing a PDP / PPO change in the connecting PLC will be registered by the polling of the Web Client using teq view refresh cycles of typical 0.6 to 2 Sec.
  • Page 119: D Haptic Effects

    Appendix D Saia-Burgess Controls AG Haptic Effects Haptic Effects D = duration in milliseconds M = magnitude S = start time in milliseconds Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 120 Appendix D Saia-Burgess Controls AG Haptic Effects Manual PCD7.D4xx │  D ocument 26-851 ENG12  │   2 016-02-05...
  • Page 121: E Contact

    Email support: ......support@saia-pcd.com Supportsite: ........ www.sbc-support.com SBC site: ........www.saia-pcd.com International Represetatives & SBC Sales Companies: ....www.saia-pcd.com/contact Postal address for returns from customers of the Swiss Sales office Saia-Burgess Controls AG Service Après-Vente Bahnhofstrasse 18 3280 Murten Switzerland...

This manual is also suitable for:

Pcd7.d435 seriesPcd7.d457 seriesPcd7.d410vtcf