1MRS755380
Fig. 4.8.1.-1
SPA Communication Parameters
4.9.
SPA/ Ethernet Adapter
Installation and Commissioning Manual
.
Locally, SPA-ZC 402 uses UTC (Coordinated Universal Time) time, which is
received from the SNTP time synchronization by default. This time format does not
use Daylight Saving Time. If you want that the IED and SPA communication uses
this time format, the IEC 61850 client has to be programmed to write the minute
offset of the UTC time to the LD0.LLN0.Daylight parameter at the defined date and
time depending on the location.

Using Dataset Editor

Dataset groups selected data, so that client can access to it easily with a single read
operation. Dataset is also the basic part of event reporting; data is linked to
spontaneous event sending only via report control blocks data set definition. Client
reads other data separately. Datasets definitions locate always under the logical
device LD0 and logical node LLN0. Dataset Editor modifies selected data set.
SPA-ZC 402
A040135
45