Chapter 7. Installation of DC Cables

7.2.3. Terminate load cables

5
1
DC Load MCB Terminal
Screw
4
Return (M/blue) Load Cable
1. Terminate the return (M/blue) cable connections to the common busbar using the
cable clamps provided. Tighten screws to a torque of 2.9Nm.
2. Terminate the live (L-/grey) cable connections at the appropriate load MCBs.
Ensure that the MCB sense wires are maintained in the load termination side of
the breaker.
3. Tighten terminal screws to a torque of 1.4Nm.

7.2.4. Refit panels (if required)

1. If it is not required to continue the installation work then re-fit the optional DC
Distribution Cover Insulator.
Procedure complete