Flexi -3G Installation & Commissioning Manual
Chapter 3. Installation Procedure
The Power Supply Unit is mounted directly on the floor.

3.1. Cabinet Position

1. Clearly identify the area where the equipment is to be installed.
Refer to the site documentation/job pack to verify cabinet position, as layout can change.
2. Measure up as per supplied floor plan and mark cabinet positions.
3. Ensure that the floor surface where the equipment is to be installed is level.
4. Ensure that the floor surface where the equipment is to be installed, and any areas over which the
equipment must be moved, are sufficiently strong to take the weight of the cabinets and the point
loading of the transport mechanism.
The mass of the cabinet is given in Cabinet Dimensions and Mass on page 74.
5. Ensure that all areas of floor are protected from damage by the transport of the equipment. Use
hardboard or a similar material. This material must be removed once installation is complete.
6. The installation area is clean and dry.

3.1.2. Positioning

No space is necessary at the sides or rear. In locating the equipment, the following must be
considered:
1. Allow distances from other equipment as required by the installation requirements of that equipment
(although the Power Supply Unit does not require space at the sides or rear, adjacent equipment
may do so).
2. Bear in mind the space required for door opening. The minimum recommended space is 840mm.
the doors are removed by opening to 45º and lifting off the hinges.
The doors are right opening (hinges on the right hand side).Do not open the door beyond 90˚
otherwise damage to the door/hinge may result.
3. When installing on a raised "Computer floor", locate the first cabinet over one tile. If load spreading
is required due to cabinet weight then this must be installed prior to cabinets being installed.
The cabinet sizes are given in Cabinet Dimensions and Mass on page 74.
4. The cabinet is suitable for mounting on concrete or other non-combustible surface only and is to be
fixed to the building floor.
5. The cabinet must be positioned in a room with restricted access.
Page 20 of 94
Document No: - 4493-CM-EN-10989402
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved