8.4. Alarm Tests
For details of all alarms and troubleshooting of those alarms, refer to the SC200 System Controller
Operation Handbook (see section 1.3. Related Information on page 5)
Alarm Type
Procedure
Rectifier Fail
Remove 1 Rectifier
Refit Rectifier after
test
Multiple
Remove more than
Rectifier Fail
1 Rectifier
Refit Rectifiers after
test
Battery Fuse
Switch off 1 Battery
Fail
MCB
Switch on the
Battery MCB after
test
Load Fuse
Switch off 1 Load
Fail
MCB
Switch on the Load
MCB after test
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved
Flexi -3G Installation & Commissioning Manual
Expected Result
On the SC200 controller the following LED(s) will be lit,
depending on system configuration: -
Minor Alarm LED
or
Major Alarm LED
On the SC200 controller the Minor Alarm LED
the Major Alarm LED
On the SC200 controller the following LED(s) will be lit,
depending on system configuration: -
Minor Alarm LED
or
Major Alarm LED
On the SC200 controller the Minor Alarm LED
the Major Alarm LED
On the SC200 controller the following LED(s) will be lit,
depending on system configuration: -
Minor Alarm LED
or
Major Alarm LED
On the SC200 controller the Minor Alarm LED
the Major Alarm LED
On the SC200 controller the following LED(s) will be lit,
depending on system configuration: -
Minor Alarm LED
or
Major Alarm LED
On the SC200 controller the Minor Alarm LED
the Major Alarm LED
Document No: - 4493-CM-EN-10989402
Chapter 8. Commissioning
(Yellow) will be lit
(Red) will be lit
(Red) will be extinguished
(Yellow) will be lit
(Red) will be lit
(Red) will be extinguished
(Yellow) will be lit
(Red) will be lit
(Red) will be extinguished
(Yellow) will be lit
(Red) will be lit
(Red) will be extinguished