Download Print this page

Eaton Flexi-3G Installation & Commissioning Manual page 44

Advertisement

Flexi -3G Installation & Commissioning Manual
Chapter 4. Battery Installation
10
10
Battery Terminal Cover
8. Refit the Battery Terminal Cover to Battery 1.
9. Check with a voltmeter that the negative terminal of battery 4 is more than 48V
negative of the positive terminal of battery 1.
10. Measure the voltage across the Battery MCB and ensure that this is less than 6V.
If more than 6V, check the battery connections to the MCB.
Page 44 of 94
Battery Cable Live (Grey) –
14
ve
Fig. 4-8 Replacing the Battery Terminal Covers
Document No: - 4493-CM-EN-10989402
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved
14
10
15
15
Battery Cable Common
(Blue)+ve

Advertisement

loading