Siemens SINAMICS G120D Operating Instructions Manual page 75

Distributed converter, control units with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Configuring the communication with a non-Siemens control
1. Import the device file (GSDML) of the inverter into the engineering tool for your control
system.
2. Configure the communication.
Configure communication with STARTER
STARTER provides a screen form to set the communication with the control system.
Open the dialog screen form "Control_Unit/Communication/Commissioning interface" and
activate the "Configure IP interfaces" tab
● Set the DHCP mode to 0 (factory setting).
● Enter the device name, address, gateway and the address for the subnet mask.
● In the Activation field select "[2] Save and activate configuration".
● To activate the settings, you must switch off the inverter power supply and then switch on
again.
You can also enter or read out data using the expert list. You can find the corresponding
parameters in the number range r8909 ... p8925
Converter with control units CU240D-2
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
4.3 Connecting the inverter to the fieldbus
Installation
75