Number
Cause
F08501
Setpoint timeout
F08502
Monitoring time sign-of-life expired
F08510
Send configuration data not valid
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting adjust-
able parameters
F08700
Communications faulty
F13100
Know-how protection: Copy protec-
tion error
F13101
Know-how protection: Copy protec-
tion cannot be activated
Converter with control units CU240D-2
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
Remedy
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the set monitoring time p2044.
Check the PROFINET connection.
Check the PROFINET configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
A CAN communications error has occurred. Check the following:
Bus cable
Baud rate (p8622)
Bit timing (p8623)
Masters
Start the CAN controller manually with p8608 = 1 after the cause of the
fault has been resolved!
The know-how protection and the copy protection for the memory card
are active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.
Alarms, faults and system messages
9.6 List of alarms and faults