Advanced commissioning
6.6 Protection functions
Setting parameters for the temperature monitoring
Parameter
p0335
p0601
p0604
p0605
p0610
p0640
p4621
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.
182
Description
Motor-cooling method (factory setting: 0)
0: Natural cooling - with fan on the motor shaft
1: Forced ventilation - with a separately driven fan
2: Liquid cooling
128: No fan
Motor temperature sensor type
0: No sensor (factory setting)
1: PTC
2: KTY84
4: Temperature switch
6: PT1000
Mot_temp_mod 2 / sensor alarm threshold (factory setting 130° C)
For monitoring the motor temperature with KTY84/PT1000.
Mot_temp_mod 1/2 / sensor threshold and temperature value (factory setting: 145° C)
For monitoring the motor temperature with KTY84/PT1000.
Motor overtemperature response (factory setting: 12)
Determines the inverter behavior when the motor temperature reaches the alarm
threshold p0604.
0: Alarm A07910, no fault.
1: Alarm A07910 and fault F07011. The inverter reduces its current limit.
2: Alarm A07910 and fault F07011.
12: Alarm A07910 and fault F07011. For use of the thermal motor model in parallel to
the temperature sensor: After switching off the supply voltage, the inverter saves the
most-recently calculated difference to the ambient air temperature. After switching the
supply voltage on again, the thermal motor model starts with 90% of the previously
saved difference temperature.
Current limit [A]
Motor temperature sensor configuration
.00
0 signal: Enable PTC short-circuit monitoring
1 signal: Disable PTC short-circuit monitoring
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD