EMC Immunity
The SINAMICS G120D drives have been tested in accordance with the immunity
requirements of category C3 (industrial) environment.
The immunity requirements apply equally to both filtered and unfiltered units.
Table 10- 9
EMC Phenomenon
Electrostatic Discharge (ESD)
Radio-frequency Electromagnet-
ic Field
Amplitude modulated
Fast Transient Bursts
Surge Voltage
1.2/50 μs
Conducted
Radio-frequency Common Mode
Mains Interruptions & Voltage
Dips
Voltage Distortion
Voltage Unbalance
Frequency Variation
Commutation Notches
Converter with control units CU240D-2
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
EMC Immunity
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 61000-2-4
EN 61000-2-4
EN 61000-2-4
EN 60146-1-1
10.9 Electromagnetic Compatibility
Level
4 kV Contact discharge
8 kV Air discharge
80 MHz ... 1000 MHz
10 V/m
80 % AM at 1 kHz
2 kV @ 5 kHz
1 kV differential (L-L)
2 kV common (L-E)
0.15 MHz ... 80 MHz
10 V/rms
80 % AM at 1 kHz
95 % dip for 3 ms
30 % dip for 10 ms
60 % dip for 100 ms
95 % dip for 5000 ms
10 % THD
3 % Negative Phase Se-
quence
Nominal 50 Hz or 60 Hz
(± 4 %)
Depth = 40 %
Area = 250 % x degrees
Technical data
Performance
Criterion
A
A
A
A
A
A
C
C
D
A
A
A
A
319