Backing up data and series commissioning
7.1 Saving settings on a memory card
7.1.2
Transferring the settings from the memory card
Download
Procedure
Proceed as follows to transfer the parameter settings from a memory card into the converter
(download):
1. Switch off the converter power supply.
2. Remove the Control Unit from the Power Module
3. Insert the memory card containing parameter settings into the Control Unit.
4. Fit the Control Unit to the Power Module - making sure that the seals are fitted correctly
and the correct tighten torque (2.0 Nm) is used to ensure the IP rating of the Inverter.
5. Connect the external 24 V supply to the Control Unit.
If the parameter data on the memory card is valid, then the inverter automatically downloads
the parameter data to it's internal memory.
242
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
Converter with control units CU240D-2