Siemens SINAMICS G120D Operating Instructions Manual page 96

Distributed converter, control units with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Commissioning
5.4 Quick commissioning with a PC
8.
9. Set the check mark for "RAM to ROM (save data in
You have entered all of the data that is necessary for the quick commissioning of your
inverter.
96
Motor identification:
• [1]: Recommended setting for closed-loop speed control. After an
ON command, the inverter identifies the motor data – and with a new
ON command, optimizes the speed controller.
• [2]: After an ON command, the inverter identifies the motor data at
standstill. Recommended setting for the following cases:
– You have selected "Speed control" as control mode, however the
– You have set "V/f control" as control mode.
• [3]: This setting only makes sense after the motor identification [2].
The inverter optimizes the speed controller at the next ON command.
• [11] or [12]: The setting is the same as [1] or [2], however with the
difference that after the motor identification, the inverter immediately
changes into the "Operation" state.
Calculating the motor parameters: Select "Complete calculation".
If you use an HTL encoder on the motor shaft for the speed control of
the inverter, either select one of the standard encoders or enter the en-
coder data.
Adapting the encoder data (Page 97)
...R: Encoder with zero mark
the drive)" to save your data in the inverter so that it
is not lost when the power fails.
Exit quick commissioning.
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD