Advanced commissioning
6.2 Inverter control
Table 6- 3
Parameter
p0757
p0758
p0759
p0760
p0761
Defining the analog input function
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755 . Parameter p0755 is assigned to the particular analog input via its index,
e.g. parameter p0755[0] is assigned to analog input 0.
Table 6- 4
CI
p1070 Main setpoint
p1075 Supplementary setpoint
p1503 Torque setpoint
p1511 Supplementary torque 1
A complete list of the connector inputs is provided in the List Manual.
Defining the analog input function - example
Advanced settings
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
For more information, please see the parameter list and the function block diagrams 2251 f
of the List Manual.
116
Parameters for the scaling characteristic and wire break monitoring
Description
x-coordinate of 1st characteristic point [V]
y coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference
speed.
x-coordinate of 2nd characteristic point [V]
y-coordinate of 2nd characteristic point [% of p200x]
Wire breakage monitoring response threshold
Connector inputs (CI) of the inverter (selection)
Significance
CI
Significance
p1522 Torque limit, upper
p2253 Technology controller setpoint 1
p2264 Technology controller actual value
In order to use the analog input AI 0 as the source for
the supplementary setpoint, you have to set
p1075 = 755[0].
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
Converter with control units CU240D-2