Bus Tie Breaker Controller Leds And Buttons - Deif GPC 300 Operator's Manual

Generator paralleling controller
Table of Contents

Advertisement

3.4.2

BUS TIE breaker controller LEDs and buttons

BUS TIE breaker buttons
No.
Item
Notes
1
Breaker
NOTE
* In Switchboard control the controller ignores the input.
BUS TIE breaker LEDs
1
No.
Item
Notes
1
Busbar A
Green : Busbar A voltage and frequency OK, and controller can close breaker.
Green flash : Busbar A voltage and frequency OK, but V&Hz OK timer running. Controller cannot close
breaker.
Yellow : Busbar A voltage and frequency are measurable, but not OK.
Red : Busbar A voltage too low to measure. Controller can close breaker.
Red flash: Blackout detection timer running and controller checking busbar A.
2
Bus tie
Off : Bus tie breaker open
Breaker
Green : Bus tie breaker closed.
Yellow flash : Synchronising or de-loading bus tie breaker.
Red flash : Bus tie breaker configuration failure, or a position failure.
Red : Tripped bus tie breaker, and trip alarm unacknowledged and/or alarm condition present.
3
Busbar B
Green : Busbar A voltage and frequency OK, and controller can close breaker.
Green flash : Busbar A voltage and frequency OK, but V&Hz OK timer running. Controller cannot close
breaker.
Yellow : Busbar A voltage and frequency are measurable, but not OK.
Red : Busbar A voltage too low to measure. Controller can close breaker.
Red flash: Blackout detection timer running and controller checking busbar A.
OPERATOR'S MANUAL 4189341171C UK
1
Close breaker : Starts close sequence. *
2
3
Open breaker : Starts open sequence. *
Page 31 of 91