Stop The Genset; Close The Genset Breaker - Deif GPC 300 Operator's Manual

Generator paralleling controller
Table of Contents

Advertisement

3.2.6

Stop the genset

Mode
Procedure
When the controller is in REMOTE mode, the engine stop is based on a remote signal, for example, from a
REMOTE
PLC.
The genset breaker must be open to stop the genset. If the genset breaker is not open, press
breaker before stopping the genset.
To stop the genset:
1. Push
2. The controller runs the cooldown period.
LOCAL
3. If Idle run stop is configured: *
4. If the genset does not stop, the controller activates an alarm.
Switchboard
When the controller is in Switchboard control, the display push-buttons are not available. The genset can only
control
be stopped locally and/or from the switchboard.
NOTE
* Idle run may not be permitted or approved by certain classification societies.
The switchboard equipment is third-party equipment. The switchboard might not include a button to stop the genset.
3.2.7

Close the genset breaker

Mode
Procedure
When the controller is in REMOTE mode, the generator breaker is closed based on a remote signal, for
REMOTE
example, from a PLC.
The genset must be running to close the genset breaker. If the genset is not running, push
genset.
To close the breaker:
1. Push
LOCAL
a. The controller synchronises the genset with the busbar. (the breaker LED flashes yellow
b. When the genset and busbar synchronise, the controller closes the breaker.
c. When the breaker is closed, the breaker LED is green
Switchboard
When the controller is in Switchboard control, the display push-buttons are not available. The genset breaker
control
can only be closed from the switchboard.
OPERATOR'S MANUAL 4189341171C UK
More information
See
Open the genset breaker
once.
If necessary, to override the cooldown time, push
Note: A genset stop without cooldown time increases the mechanical wear of the genset. The genset
may also have problems if it needs to restart immediately. The genset should only be stopped without
cooldown time in emergencies. Contact the genset manufacturer for more information.
The controller runs the Idle run stop sequence.
If needed, to override the Idle run stop , push
More information
See
Start the genset
for more information.
to close the genset breaker.
If the genset and busbar are not synchronised before the synchronisation timer expires, the breaker
does not close. The synchronisation failure alarm is activated.
for more information.
again.
again.
.
to open the
to start the
).
Page 24 of 91