3.5

Operator messages

3.5.1

Controller status texts

The controller status texts are shown at the top of the display. The status text shown depends on the type of controller. Not all texts
apply for all controller types.
Status text *
-
Alarm testing
BTB in operation
Cooldown - # s
Crank off
Crank on
De-loading GB
De-loading MAINS **
Dividing section
Engine stopping
Fixed power
Fixed frequency
Frequency droop
Frequency too high
Frequency too low
Load sharing
Not ready for operation
Ready for operation
MAINS in operation
MAINS not ready
MAINS ready
Manual regulation
Start prepare - # s
Stop coil activated - # s
Synchronising GB
Synchronising sections
Synchronising MB **
Waiting for software
NOTE
* "# s" represents a timer countdown.
NOTE
** Applicable to both MAINS controller and SINGLE genset with mains breaker.
OPERATOR'S MANUAL 4189341171C UK
Description
Cannot read controller status. For example, slow communication or a loss of communication.
Enable alarm test parameter is enabled.
The bus tie breaker is closed.
The remaining time (in seconds) for the genset cooldown.
The crank is turned off if there is no running detection of the genset during start.
The crank is activated in order to start the genset.
The controller is de-loading the generator breaker.
The controller is broadcasting a set point for de-loading the mains breaker.
The controller is broadcasting set points for de-loading the bus tie breaker.
The genset is being stopped.
The genset is running and is being regulated to a fixed power.
The genset is running and is being regulated using fixed frequency regulation.
The genset is running and is being regulated using frequency droop regulation.
The frequency is too high and should be adjusted to a lower value.
The frequency is too low and should be adjusted to a higher value.
The gensets that are connected to the busbar are sharing the load symmetrically with each other.
The controller is not ready for operation. For gensets Start enable might not activated, or there are
alarms (latched or unacknowledged) blocking the ready status.
All operation conditions are met. Gensets are ready to start and/or breakers are ready to close.
MAINS supply is available, and mains breaker is closed.
MAINS is not ready to provide power to the busbar. There may be alarms blocking the mains breaker
from closing.
MAINS supply is available, and mains breaker is open.
The genset is running and is under manual regulation.
The remaining time (in seconds) for the genset to prepare to start.
The remaining time (in seconds) before the genset shuts down.
The controller is synchronising the genset to the busbar frequency and voltage to close the generator
breaker.
The controller is broadcasting the set points for synchronisation.
The controller is broadcasting a set point for synchronisation.
A software update is in progress.