6.6.2
Configure a curve
Curves can only be configured if the curve function is assigned in the input/output configuration. When a curve function is assigned,
the parameter is shown in the parameter list.
Example
Function assigned to an analogue input (AI):
Engine > Power derate > Temperature > Derate 1 temperature
Parameter now available under:
Engine > Power derate > Temperature > Derate 1
1. Select Setup from the parameter page.
•
The curve is shown:
Switchboard control
Home / Configure / Parameters / Curve
Derate curve
100.0
80.0
-100.0
Edit
•
2. Select Edit to configure the curve settings:
Switchboard control
Home / Configure / Parameters / Cruve / Curve edit
Derate curve
X [°C]
#
1
-99
2
90
3
130
4
200
View
•
3. Configure the curve settings:
•
View to display the curve or write the settings.
•
Add a new empty set of coordinates (X,Y), max. 10 sets per curve.
•
Remove a set of coordinates, min. of four sets is required.
•
Column to change between X or Y settings.
•
Select
OK to edit the value.
4. Select View and then Write to save the curve settings.