3.2.8

Open the genset breaker

Mode
Procedure
When the controller is in REMOTE mode, the generator breaker is opened based on a remote signal, for
REMOTE
example, from a PLC.
To open the genset breaker:
1. Push
a. If load sharing is present, the controller de-loads the breaker until the load is less than the de-load
LOCAL
b. The controller then opens the generator breaker. The breaker LED is OFF when the breaker is open.
c. If load sharing is not present or not possible, the controller immediately opens the generator breaker.
d. The breaker LED is OFF when the breaker is open.
Switchboard
When the controller is in Switchboard control, the display push-buttons are not available. The breaker can
control
only be opened from the switchboard.
NOTE
* If there is a position failure for the breaker, you can still attempt to try and open the breaker and push
OPERATOR'S MANUAL 4189341171C UK
to open the genset breaker. *
open point (the breaker LED flashes yellow
).
.
Page 25 of 91