Remove From Service; Silence Horn - Deif GPC 300 Operator's Manual

Generator paralleling controller
Table of Contents

Advertisement

The alarm is marked as shelved (
The alarm action (protection) is inactive until the alarm is unshelved.
Unshelve an alarm
1. Select the shelved alarm.
2. On the details page, select Service.
3. Select Unshelve.
7.1.3

Remove from service

Alarm action not active
An alarm that is removed from service is no longer active.
The alarm remains out of service until it is returned back to service.
Remove an alarm from service
You can only remove certain types of alarms from service.
1. Select the alarm.
2. On the details page, select Service.
3. Select Remove from service.
4. The alarm is now removed from service.
The alarm is marked as out of service (
Return an alarm to service
1. Select the alarm.
2. On the details page, select Service.
3. Select Return to service.
4. The alarm is now returned to service.
If the alarm condition is still present, the alarm is activated again.
7.1.4

Silence horn

The controller must be configured with horn outputs for the silence horn push-button to work. When an alarm occurs the horn output
activates.
Push
Silence horn to deactivate all horn outputs. The push-button does not have any other effect on the alarm system. If a new
alarm occurs after the button is pushed, the horn output restarts.
Example of the Silence horn button
(1)
Alarm 1
(2)
(3)
Horn
OPERATOR'S MANUAL 4189341171C UK
or
) in the alarm list.
CAUTION
or
) in the alarm list.
Silence
Silence
pushed
pushed