4
START-UP PROCEDURE
This chapter describes the procedures before operation.
4.1

Overview

This section describes an outline of the procedure before operation for each CPU module.

Procedure for process mode

This section describes an outline of the procedure when using the Process CPU (process mode).
The procedure for starting up a redundant system is partially different.
For the procedure to start up a redundant system, refer to the following.
Page 54 PROCEDURE FOR STARTING UP A REDUNDANT SYSTEM
1.
Installing a Battery
Install a battery to the CPU module. ( Page 38 Installing a Battery)
2.
Inserting an extended SRAM cassette or an SD memory card
Insert an extended SRAM cassette or an SD memory card to the CPU module as needed. ( Page 39 Inserting or
Removing an Extended SRAM Cassette,  Page 40 Inserting and Removing an SD Memory Card)
3.
Mounting modules and connecting cables
Mount modules on the base unit, and connect cables. ( MELSEC iQ-R Module Configuration Manual)
4.
Powering on the system
Check the following before powering on the system.
• A cable is correctly connected to the power supply.
• Power supply voltage is within the specified range.
• The CPU module is in the STOP state.
• A personal computer on which an engineering tool has been installed is connected to the CPU module. ( Page 42
Connecting a Personal Computer)
5.
Powering on the personal computer
Power on the personal computer on which the engineering tool has been installed (the personal computer connected to the
CPU module).
6.
Starting up the engineering tool
Start up the engineering tool that has been installed on the personal computer connected to the CPU module.
4 START-UP PROCEDURE