Mitsubishi Electric MELSEC iQ-R Series User Manual page 401

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Global device setting
Set devices and their ranges for each tracking block No.
[CPU Parameter]  [Redundant System Settings]  [Tracking Setting]  [Device/Label Detailed Setting]  [Global
Device Setting]
Window
Displayed items
Item
Device Setting Reflection
Tracking Block No.
File Register Setting
Device
Start/End
• To input devices and their ranges set in "Device/Label Memory Area Setting" in a batch, click the [Device
Setting Reflection] button.
• When using the SFC program, set all points of step relay (S) within the device transfer range.
Description
Reflects the device setting of "Device/Label Memory Area Setting" in the CPU parameter.
(Except for the annunciator (F), link special relay (SB), and link special register (SW))
Select the number of a tracking block to be set.
Enter a file name of the file register file.
This item is valid only when the file register (ZR) is selected in the device name field.
Select a device to be transferred. ( Page 390 Devices that can be specified)
Specify a range of devices to be transferred.
26 REDUNDANT FUNCTION
26.3 Tracking Transfer
26
399