Error
Error name
code
2520H
Invalid interrupt
2521H
2522H
Invalid interrupt
2610H
Inter-module
synchronization
signal error
2611H
2630H
Multiple CPU
synchronization
signal error
2631H
2800H
I/O number or
network number
specification
error
2801H
2802H
I/O number or
network number
specification
error
36 ERROR CODES
576
36.4 List of Error Codes
Error details and cause
• Even though an interrupt was
requested, there is no interrupt factor.
• An interrupt was requested from the
module with no interrupt pointer
setting.
• An execution interval error of the
synchronization interrupt program has
been detected.
• An inter-module synchronization error
has been detected.
• An inter-module synchronization error
has been detected.
• An error of the module set as the
inter-module synchronous master has
been detected.
• An execution interval error of the
synchronization interrupt program has
been detected.
• A multiple CPU synchronization error
has been detected.
• A multiple CPU synchronization error
has been detected.
• The specified I/O number is out of
range (other than 0 to FFH, 3E0 to
3E3H).
• The I/O number of the module that
does not exist was specified.
• The I/O number of the module that
does not support the instruction was
specified.
• The dedicated instruction specified in
the program cannot be executed in
the specified module or mode.
Stop/
Action
continue
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module, base unit, or module
(I/O module or intelligent function
module) connected. Please
consult your local Mitsubishi
representative.
Stop
• Check and correct the interrupt
pointer setting in the module
parameters.
• Take measures so that no
interrupt is requested from the
module with no interrupt pointer
setting.
• Check and correct the interrupt
setting in the buffer memory of the
intelligent function module.
• Correct the BASIC program
executed in the QD51.
Stop/
• Check the module set as the inter-
continue
module synchronous master.
• Correct the inter-module
synchronous master settings.
• Take measures to reduce noise.
• Reset the CPU module and run it
Stop
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module, base unit, extension
cable, or module (I/O module or
intelligent function module)
connected. Please consult your
local Mitsubishi representative.
Stop/
• Take measures to reduce noise.
continue
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module or base unit. Please
Stop
consult your local Mitsubishi
representative.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
Stop/
tool, display the error program
continue
(step) by clicking the [Error Jump]
button, and correct the program.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Check the execution propriety
(including support status and
execution mode) of the dedicated
instruction, referring to the manual
for the target module.
Detailed
Diagnostic
information
timing
System
At interrupt
configuration
occurrence
information
System
At interrupt
configuration
occurrence
information
Always
System
At power-on, at
configuration
RESET, at
information
END
instruction
execution
Always
System
At power-on, at
configuration
RESET, at
information
END
instruction
execution
Error location
At instruction
information
execution
Error location
At instruction
information,
execution
system
configuration
information
Error location
At instruction
information,
execution
system
configuration
information