• Details of each data
No.
Item
Description
(1)
Identification code
"MRCB" is output.
(2)
File version
"1" is displayed.
(3)
File type
The file type is output. (fixed to 1: Continuous/trigger logging)
(4)
Model information
The module model name that outputted binary file is output. RCPU is output to the first eight bytes
and 00H is output to the last eight bytes.
(5)
Added-data
The output selection setting for the data that can be output is output.
information
b0 1: Output date and time data.
b1 1: Output a data collection interval.
b2 1: Output an execution step No.
b3 1: Output an execution program name and No.
b4 1: Output a trigger flag.
b5 1: Output index.
b6 1: Output device comments.
b7 1: Output comments.
b9 1: Output device comments for each program.
(6)
Comment size
The comment length of (7) Comment is output.
(7)
Comment
The comment specified in the setting is output in Unicode.
(8)
Number of collected
The number of data points of the data information ((9) to (17) and (29) to (31)) for data logging is output.
data
(9)
Data information size
The total size of the data information ((9) to (17) and (29) to (31)) for data logging is output.
(10)
Data type
The numeric value shown below is output depending on the data type.
0000H: Bit
0001H: Word (signed)
0002H: Double word (unsigned)
0003H: Word (signed)
0004H: Double word (unsigned)
0005H: Single-precision real number
0006H: Double-precision real number
0007H: String
0008H: Numeric string
0009H: Time
(11)
Output format
The same numerical value as the value in (10) Data type is output. However, when the data type is bit,
character string, numeric string, or time, FFFFH is output because the output type cannot be specified.
(12)
Data information
The data-related information is output.
setting
b2 1: Device comment specified
b3 1: Device code specified
b4 1: Program name length/program name specified
(13)
Data length
The data length of data is output. When the data type is the bit type, it will be output as two bytes.
(14)
Data name length
The length of the data name specified in the setting is output.
(15)
Data name
The data name specified in the setting is output in Unicode.
(16)
Device comment
The length of the device comment name specified in the setting is output.
name length
(17)
Device comment
The device comment name specified in the setting is output in Unicode.
name
When the device comment file for each program or the comment of the corresponding program does
not exist, the comment of the device comment file is output.
b9
b7 b6 b5 b4 b3 b2 b1 b0
0: Do not output date and time data.
0: Do not output a data collection interval.
0: Do not output an execution step No.
0: Do not output an execution program name or No.
0: Do not output a trigger flag.
0: Do not output index.
0: Do not output device comments.
0: Do not output comments.
0: Do not output device comments for each program.
b4 b3 b2
0: Device comment not specified
0: Device code not specified
0: Program name length/program name not specified
*1
Size (byte)
4
1
1
16
2
2
2 to 512
2
2
2
2
2
2
2
2 to 512
2
0 to 2048