Mitsubishi Electric MELSEC iQ-R Series User Manual page 561

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
1B60H
Standby system
• In backup mode, the standby system
CPU module
CPU module has not started up. (The
error
error is detected in the control
system.)
1B61H
Standby system
• In backup mode, a stop error of the
CPU module
standby system CPU module was
error
detected. (The error is detected in the
control system.)
1B70H
Tracking
• Data communications with the other
communications
system cannot be performed even in
disabled
backup mode. (The error is detected
in the control system or the standby
system.)
1B71H
Tracking
• Data communications with the other
communication
system cannot be performed in one of
error
the two tracking cables even in
backup mode. (The error is detected
in the control system or the standby
system.)
Stop/
Action
continue
Continue
• If the standby system is powered
off, power on the system.
• If the standby system CPU module
is in the RESET state, clear the
RESET state. If the same error
code is displayed again, the
possible cause is a hardware
failure of the CPU module. Please
consult your local Mitsubishi
representative.
Continue
• Eliminate the error cause, and
restart the system. If the same
error code is displayed again, the
possible cause is a hardware
failure of the CPU module. Please
consult your local Mitsubishi
representative.
Continue
• If the standby system is powered
off, power on the system.
• If a WDT error has occurred in the
other system CPU module,
eliminate the error cause, and
restart the system.
• Connect tracking cables securely
and properly to the connectors of
the redundant function modules in
both systems. (One cable shall be
connected between the IN
connector of the module in system
A and the OUT connector of the
module in system B. The other
cable shall be connected between
the OUT connector of the module
in system A and the IN connector
of the module in system B.)
• Take measures to reduce noise. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module, redundant function
module, base unit, or tracking
cable. Please consult your local
Mitsubishi representative.
Continue
• Connect tracking cables securely
and properly to the connectors of
the redundant function modules in
both systems.
• Take measures to reduce noise. If
the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module or tracking cable.
Please consult your local
Mitsubishi representative.
Detailed
Diagnostic
information
timing
Always
Always
Always
Always
36 ERROR CODES
559
36.4 List of Error Codes
36

Advertisement

Table of Contents
loading

Table of Contents