15.3

Error Clear

This function clears all the existing continuation errors at once.
A continuation
error occurs.
• Power shutdown
• Battery failure
• Constant scan time exceeded
Errors that can be cleared
This function can be used to clear only the continuation errors listed in the following table.
Error name
Power shutoff
Power shutoff (either of the redundant power supply modules)
Failure (either of the redundant power supply modules)
Invalid power supply module
Power supply module configuration error
ROM write count error
Battery error
Memory card access error
SNTP clock setting error
Default gateway/gateway IP address error
Own node port number error
Open specification port number error
Specified IP address error
Connection establishment failed
Socket communications response send error
TCP connection timeout
IP address error
Connection number acquisition error
Receive buffer securement error
UDP/IP send failed
TCP/IP send failed
Unsend data send error
Redundant IP address error
PID operation error
Module moderate error
Another CPU module moderate error
Inter-module synchronization processing error
Multiple CPU synchronization processing error
Annunciator ON
Operation continuation error
Receive queue full
Receive processing error
Transient data error
Constant scan time error
Network configuration mismatch
15 RAS FUNCTIONS
208
15.3 Error Clear
A continuation
error occurs.
Clears the error.
Engineering tool
Error code
1000H
1010H
1020H
1030H
1031H
1080H
1090H
1100H
1120H
1124H
1128H
1129H
112DH
112EH
1133H
1134H
1152H
1155H
1157H
1165H
1166H
1167H
1180H
11A0H to 11B8H
1200H, 1210H
1220H
1240H, 1241H
1260H, 1262H
1800H
1810H
1830H
1831H
1832H
1900H
1B00H
No continuation
error occurs.