Error
Error name
Error details and cause
code
2320H
Remote
• The start I/O number of the remote
password
password target module is set to other
setting error
than 0H to 0FF0H.
• There is a problem on the slot
specified by the start I/O number of
the remote password setting.
(1) No module is mounted.
(2) The mounted intelligent function
module does not support the remote
password setting.
2321H
Remote
• In a multiple CPU system, the module
password
controlled by another CPU module is
setting error
specified by the start I/O number of
the remote password setting.
2400H
Module
• The module information at power-on
verification error
differs from the information of
modules actually mounted.
• The I/O module or intelligent function
module is not mounted properly or
was removed during operation.
2401H
Module
• A CPU module, I/O module, or
verification error
intelligent function module was
mounted on the base unit during
operation.
2420H
Fuse blown
• The output module with a blown fuse
error
has been detected.
Stop/
Action
continue
Stop
• Set the start I/O number of the
remote password target module
within the range 0H to 0FF0H.
• On the specified slot, mount an
intelligent function module that
supports the remote password
setting.
Stop
• Check and correct the remote
password setting.
Stop/
• Check the detailed information
continue
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool and check the module
corresponding to the displayed
slot number.
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
error module. Please consult your
local Mitsubishi representative.
Stop/
• Check the detailed information
continue
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool and check the module
corresponding to the displayed
slot number.
• Do not mount a CPU module, I/O
module, nor intelligent function
module during operation.
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
error module. Please consult your
local Mitsubishi representative.
Stop/
• Check the FUSE LED of each
continue
output module, and replace the
one with the FUSE LED on.
• Check the detailed information
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool, and replace the module
corresponding to the displayed
slot number.
Detailed
Diagnostic
information
timing
System
At power-on, at
configuration
RESET, at
STOP  RUN
information
state
System
At power-on, at
configuration
RESET, at
STOP  RUN
information
state
System
Always
configuration
information
System
Always
configuration
information
System
Always
configuration
information
36 ERROR CODES
571
36.4 List of Error Codes