Error
Error name
code
424CH
Redundant system related
error
424EH
Redundant system related
error
424FH
Redundant system related
error
4251H
Redundant system related
error
4252H
Redundant system related
error
4256H
Redundant system related
error
4258H
Redundant system related
error
4259H
Redundant system related
error
425AH
Redundant system related
error
425BH
Redundant system related
error
425EH
Redundant system related
error
425FH
Redundant system related
error
4269H
Any other error
4270H
Debug related function
error
4271H
Debug related function
error
Error details and cause
• The request cannot be executed because the
online program change function is being
executed.
• The request cannot be executed because an
unsupported system switching is specified.
• The request cannot be executed because system
switching due to a different cause was executed
during execution of system switching by the
engineering tool.
• The request cannot be executed because the
redundant system is in separate mode.
• The systems cannot be switched because an
error has occurred in an intelligent function
module of the standby system.
• The request cannot be executed because a
timeout error has occurred in tracking
communications.
• The operation mode cannot be changed because
the control system in separate mode is in a state
waiting for transition to RUN.
• The operation mode cannot be changed from
separate mode to backup mode because the
communication route differs from that of when the
mode was changed from backup mode to
separate mode.
The system cannot be started as the control system
because of either of the following reasons:
• The system A/B setting has not been determined.
• The system is being changed to the control
system.
• A start-up operation has been performed in the
standby system.
• In a redundant system with redundant extension
base unit, a function that is not supported by an
intelligent function module on an extension base
unit has been executed via the intelligent function
module.
• Data communications cannot be performed with
the other system because a module
communication test is being executed on a
redundant function module.
• The memory copy function cannot be executed
because the CPU module models differ between
the control system and the standby system.
• The remote RUN (function) cannot be executed.
• Data logging is being performed (data logging
status: RUN waiting (no collection), Condition
waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting
(collecting before trigger), Collecting after trigger,
or Saving the logging data) to another memory.
• The specified data logging is already being
performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start
waiting (no collection), Pause, Collecting, Trigger
waiting (collecting before trigger), Collecting after
trigger, or Saving the logging data).
Action
• Execute the request again after the online program change
processing ends.
• Take measures to reduce noise, and execute the request
again. If the same error code is displayed again, the possible
cause is a hardware failure of the target module. Please
consult your local Mitsubishi representative.
• Check that the systems are switched successfully. If not,
monitor SD1644 (Cause of system switching failure),
eliminate the error cause, and then execute the function
again.
• Change the operation mode to backup mode, and execute
the request again.
• Identify an error module by monitoring SD1646 (System
switching request status from a network module of the other
system), eliminate the error cause, and then switch the
systems again.
• Check if the tracking cables have been properly connected. If
the same error code is displayed again even after the
tracking cables are connected properly, the possible cause is
a hardware failure of the CPU module, redundant function
module, or tracking cable. Please consult your local
Mitsubishi representative.
• Change the operating status of the CPU module whose
PROGRAM RUN LED is flashing to RUN by using the RUN/
STOP/RESET switch or remote operation, and change the
operation mode again.
• Change the operation mode using the same communication
route of when the mode was changed from backup mode to
separate mode.
Take the following actions:
• Set one system as system A and the other system as system
B, restart the CPU module.
• Check that the system has been changed to the control
system.
• Check the system status (control system/standby system).
• Execute the function via a module on the main base unit.
• Check the command data of the SLMP/MC protocol.
• Retry data communications after the module communication
test ends.
• Match the CPU module model between the systems, and
execute the function again.
• Execute the function again after a while.
• Register data logging to the memory where the data logging
is being performed. Or, stop the data logging being
performed and register again.
■When CPU Module Logging Configuration Tool is used
• Start the data logging to the memory where the data logging
is being performed. Or, stop the data logging being
performed, and start the data logging.
• Stop the data logging. Or, write, delete, or register data
logging to the setting number where no data logging is being
performed.
36 ERROR CODES
36.4 List of Error Codes