Connections - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

6

CONNECTIONS

Compared with HGM420N, HGM410N has no Mains Voltage 3-phase input terminals. The rear panel of
HGM420N is as below.
Pin
Function
1
B-
2
B+
3
Aux. Output 1
4
Crank
5
Aux. Output 2
6
Aux. Output 3
HGM400N Series Genset Controller User Manual
Fig.2 Controller Rear Panel
Table 6 Terminal Connection Description
Cable Size
2.5mm
2
Connected with negative of starter battery.
Connected with positive of starter battery. If wire
2.5mm
2
length is over 30m, better to double wires in parallel.
Max. 20A fuse is recommended.
B+ is supplied by 2 point, rated
1.5mm
2
5A.
B+ is supplied by 2 point, rated
1.5mm
2
5A.
B+ is supplied by 2 point, rated
1.5mm
2
5A.
B+ is supplied by 2 point, rated
1.5mm
2
5A.
Description