Smartgen HGM400N Series User Manual page 5

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

generator, controller has over voltage, under voltage, over frequency, under frequency, over current
and over power detection functions;
 Precisely collect and display all parameters of engine:
Temp. (WT)
Oil pressure (OP)
Fuel Level (FL)
Engine Speed (RPM)
Battery Voltage (VB)
Charger Voltage (VD)
Hours Counter (HC)
Start times
 Control and protection function: automatic start/stop of the genset, ATS (Auto Transfer Switch)
control and perfect fault indication and protection function;
 ETS (Energize to stop), idle control, pre-heat control, speed raise control and speed drop control
functions, and all output ports are relay outputs;
 Parameter setting function: allows users to modify and set the parameters and meanwhile will be
stored in internal FLASH and won't be lost even in case of power outage; all controller parameters
can be adjusted on front panel of the controller or via USB interface on PC;
 Multiplex input port 3 and 4 can be used in various occasions: input 3 can be used as auxiliary input
port or fuel level sensor, while input 4 can be used as auxiliary input port or configurable sensor;
 Multiple temperature, oil pressure, and fuel level sensors can be used directly, and parameters can
be user-defined;
 One configurable sensor: can be set to temperature sensor, oil pressure sensor or fuel level sensor,
which enables the detection of double temperatures, double oil-pressures and double fuel levels.
 Multiple crank disconnect conditions (magnetic pickup, oil pressure, generator) are optional;
 Emergency start function;
 Flywheel teeth auto-recognition function;
 Wide power supply range: DC(8~35)V, which suitable for different starting battery voltage
environments;
 All parameters apply digital adjustment, instead of conventional analog modulation with normal
potentiometer, improving the wholesome reliability and stability;
 Maintenance function: types can be set to date or running time. Actions (inactive, warning, alarm
shutdown) can also be set when maintenance time is out;
 Event log function (max. 99 pieces of records), real-time clock, and schedule to start/stop generator
function (start once monthly/weekly/daily on/off load can be set);
 IP55 waterproofness with rubber-ring gasket between enclosure and screen;
 Metal fixing clips are used to fix the controller;
 Modular design, self-extinguished ABS plastic enclosure, pluggable connection terminals and
embedded installation way; compact structure with easy mounting.
HGM400N Series Genset Controller User Manual
°C/°F
kPa/psi/bar
%
Residual Fuel Level
r/min
V
V
L