Protection; Warning - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

5

PROTECTION

5.1

WARNING

When controller detects warning alarms, it only gives warnings not shutdown. The alarm information will
be displayed on LCD.
No.
Items
1
High Temp.
2
Low Oil Pressure
3
Gen Over Current
4
Fail to Stop
5
Low Fuel Level
6
Charge Alt Failure
7
Battery Under Volt
8
Battery Over Volt
9
Aux. Input
10
Loss of Speed Signal
HGM400N Series Genset Controller User Manual
Table 4 Warning Alarms
When the controller detects that temperature has exceeded the pre-set
value while shutdown is prohibited, or detects that the Aux. input high
temperature while shutdown is prohibited, it will initiate a warning alarm
and the corresponding alarm information will be displayed on LCD.
When the controller detects that the oil pressure has fallen below the
pre-set value while shutdown is prohibited, or detects that the Aux. input
low oil pressure while shutdown is prohibited, it will initiate a warning alarm
and the corresponding alarm information will be displayed on LCD.
When the controller detects that the genset current has exceeded the
pre-set value and the over current delay has expired, it will initiate a
warning alarm and the corresponding alarm information will be displayed
on LCD.
After "fail to stop" delay/ETS delay has expired, if gen-set does not stop
completely, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the fuel level has fallen below the pre-set
value while shutdown is prohibited, or detects that the Aux. input low fuel
level while shutdown is prohibited, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that charger voltage has fallen below the
pre-set value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that battery voltage has fallen below the
pre-set value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that battery voltage has exceeded the pre-set
value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the auxiliary input warning signals, it will
initiate a warning alarm and the corresponding alarm information will be
displayed on LCD.
When the controller detects that the engine speed is 0 and the delay is 0, it
will initiate a warning alarm and the corresponding alarm information will
be displayed on LCD.
Description