Smartgen HGM400N Series User Manual page 23

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

No.
Items
85
Gen Over Volt Warn
86
Gen Under Volt Warn
87
Gen Over Freq Warn
88
Gen Under Freq Warn
Gen Over Current Warn
89
Percentage
90
High Temp. Warn
91
Low OP Warn
92
Aux. Sensor Warn
93
Gen Over Volt Delay
94
Gen Over Freq Delay
HGM400N Series Genset Controller User Manual
Range
Default
(30-620)V
253
(30-620)V
193
(0-75.0)Hz
55.0
(0-75.0)Hz
42.0
(50-130)%
110
(80-140)°C
95
(0-400)kPa
124
(80-140)°C
(0-400)kPa
95
(0-100)%
(0-20.0)s
10.0
(0-20.0)s
2.0
Description
signal via configurable input port)
When genset voltage is over the point,
generator over voltage is active. When the
point is 620V, it does not detect over voltage
signal.
When generator voltage is under the point,
generator under voltage is active. When the
point is 30V, it does not detect under voltage
signal.
When generator frequency is over the point,
over frequency is active, gen over frequency
signal will be sent.
When generator frequency is lower than the
point, under frequency is active, gen under
frequency signal will be sent.
When load current is over the point, over
current is active. When this value is 0, warn
alarm signal won't be sent.
When the temperature value of the external
temperature sensor exceeds the set value,
"High Temperature" timer is initiated. Detecting
only after safety on delay has expired. If the set
value is 140, high temperature signal will not
be
sent
(this
only
temperature sensor, not high temperature
signal via config. input port).
When the external pressure sensor value falls
below this set value, "Low Oil Pressure" timer is
initiated. Detecting only after safety on delay
has expired. If the set value is 0, low oil
pressure signal will not be sent (this only
concerns pressure sensor and does not
concern low oil pressure warning signal via
configurable input port)
Respective corresponding with 90 temp.
sensor, 91 pressure sensor and 84 level sensor
in this table.
When generator voltage exceeds shutdown
value and last for a while, gen over volt
shutdown is active.
When generator frequency exceeds shutdown
value and last for a while, gen over freq
shutdown is active.
concerns
external
Page 23 of 38